Electrical Application Details for App #: M391602
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 31 WEST 12 STREET MANHATTAN BIN: 1009627     Block: 576   Lot: 56
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 31 W 12 ST Census Tract:   63 Health Area:  5700
SIDEWALK Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):    5 AVENUE,    AVENUE OF THE AMERICAS
Status:   C - JOB IS SIGNED OFF 02/10/2020
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/31/2017 6:16 AM
Application Entered:   01/31/2017 Job Start Date:   01/31/2017
Last Change:   02/10/2020 Job End Date:   01/31/2018
Appointment Status:   
Last Inspection By:   CARLOS CARDONA       On     02/08/2020      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010285 Licensee Name: GREGORY PAPANTONIOU
Firm: 003867 Firm Name: BOROWIDE ELECT'L CONTR'S
Firm Phone: 718-204-1347  Firm Address: 36-07 20TH AVENUE INC ASTORIA NY 11105 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
W - SIDEWALK SHED WIRING & LIGHTING
Total Fee:  $40.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: EVEREST SCAFFOLDING
Authorized Representative:  JIMMY DOWNES
Relationship To Owner:   CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
SWK                     
Buildings Total                     
Total Units : 5 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/01/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  TEMPORARY SHED LIGHTING WE ARE NOT RESPONSIBLE FOR FEED OR MAINTAINING LIGHTS

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: M391602
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/01/2019 04/01/2019 AGF V (29) (4)
INSPECTION COMMENTS: FAIL ... OBJECTIONS ISSUED . FOR SIDE - WALK SHED ; INSUFFICIENT GROUNDING FOR SEPARATE STRUCTURE , GFCI NON OPERABLE , AND LACKING CONDUIT SUPPORT .
 
(2) 02/08/2020 02/10/2020 CDX C R (8) (0)
INSPECTION COMMENTS: PASS. SHED REMOVED. SEE ATTACHMENT.

OBJECTION FOR APPLICATION #: M391602
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(OPEN SPACE) SEPARATE STRUCTURE NOT PROPERLY GROUNDED , ART. 250
RSLV 04/01/2019 04/01/2019 02/08/2020
 
002 (999) OTHER
(OPEN SPACE) GFCI INSTALLED OUTDOORS IS NOT WR TYPE , ART. 408
RSLV 04/01/2019 04/01/2019 02/08/2020
 
003 (999) OTHER
(OPEN SPACE)GFCI INSTALLED IS NON OPERABLE , DOES NOT TRIP WHEN TESTED , ART.110
RSLV 04/01/2019 04/01/2019 02/08/2020
 
004 (999) OTHER
(OPEN SPACE)IMC SUPPORT IS INSUFFICIENT , CONDUIT IS SUBSIDING THROUGHOUTCERTAIN POINTS , ART. 342
RSLV 04/01/2019 04/01/2019 02/08/2020