Electrical Application Details for App #: B408844
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 117 LIVINGSTON STREET BROOKLYN BIN: 3425971     Block: 154   Lot: 40
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 415 RED HOOK LANE Census Tract:   37 Health Area:  2400
ALL FLOORS SERVED, MR Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
Related Job Number:    320626747
DOB Cross Street(s):       BOERUM PLACE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/17/2016 7:47 PM
Application Entered:   03/17/2016 Job Start Date:   03/20/2016
Last Change:   08/22/2025 Job End Date:   03/20/2019
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   JOHN HUGHES       On     06/21/2019      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 011986 Licensee Name: ANTHONY LUCIANO
Firm: 003652 Firm Name: JAM ELECTRICAL CORP
Firm Phone: 212-265-0142  Firm Address: 1133 6TH AVE 28TH FLOOR NEW YORK NY 10036 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $622.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: TIMOTHY QUINLAN
Owner Business Name: RED HOOK LANE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  ELEVATORS
B. Each Additional 10 Floors Or Less  4  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 06/25/2019
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  INSTALLATION OF ELEVATORS BY ELEVATOR COMPANY IN CONJUNCTION WITH ELEVATOR APPLICATION(273018E). ELEVATOR CONTROL AND LOAD SIDE WIRING ONLY. POWER TO CONTROL, 110V LIGHTING, MR,PIT GFCI BY OTHERS ROT-132

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: B408844
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/29/2017 08/30/2017 DNM N (24) (0) Y
INSPECTION COMMENTS: ELECTRICIAN DID NOT SHOW.
 
(2) 09/11/2017 09/11/2017 CJH N (42) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(3) 11/29/2017 12/07/2017 SGY N (45) (0) Y
INSPECTION COMMENTS: NO ACCESS
 
(4) 06/21/2019 06/25/2019 JGX V (63) (2)
INSPECTION COMMENTS: INSPECTION COMPLETED. 2 OBJECTIONS ISSUED.

OBJECTION FOR APPLICATION #: B408844
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (127) NO GROUND HAS BEEN PROVIDED FOR SEPARATELY DERIVED SYSTEM
(ROOF) TRANSFORMER EGC'S NOT PROPERLY INSTALLED. ART. 250.30
OPEN 06/21/2019 06/21/2019
 
002 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
(ROOF) 480V CONDUCTORS NOT PROPERLY COLOR CODED AT TRANSFORMERS ANDCONTROLLERS. ART. 210.5
OPEN 06/21/2019 06/21/2019