Electrical Application Details for App #: Y140698
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 976 TINTON AVENUE BRONX BIN: 2004826     Block: 2669   Lot: 9
   

DOB NOW: Inspections


Filed: 976 TINTON AV Census Tract:   133 Health Area:  3500
ENTIRE/2108590 Admin Area:   Y - BRONX Inspection Area:   C
BRONX, NY 10456 Community Board:   203
DOB Cross Street(s):   EAST 163 STREET,    EAST 165 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   P - PICK-UP eFiled:   NO
Application Entered:   03/05/2008 Job Start Date:  
Last Change:   08/22/2025 Job End Date:  
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     02/16/2008      
Field Disp:   W - ISSUE OBJECTION TO OWNER
Energize Recommendation:  
Objection Disposition:  

License #: Licensee Name: UNKNOWN
Firm: Firm Name: UNKNOWN
Firm Phone:   Firm Address:  

Work Started or Filed by Others: NO
Work Category:    Work To Be Done:   Total Fee:  $0.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: TINTON 976 REALTY LL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 03/05/2008
Power Issued: Response:  

Follow-Up: V - OWNER OBJECTION 03/05/2008
Contractor's Comments:  

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: Y140698
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/16/2008 03/05/2008 GYM W (30) (12)
INSPECTION COMMENTS: VIOL

OBJECTION FOR APPLICATION #: Y140698
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
BSMT MDP PNL REEDS ER, LATERAL CONTR
OPEN 02/16/2008 02/16/2008
 
002 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
200A SER SW NEUTRAL NOT BONDED TO ENCL
OPEN 02/16/2008 02/16/2008
 
003 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
A)FEEDS,PNLS,APT#26,16,56,44,35,32,40,30,14,15,
OPEN 02/16/2008 02/16/2008
 
004 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
BSMT THRU OUT
OPEN 02/16/2008 02/16/2008
 
005 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
BSMT THRU OUT
OPEN 02/16/2008 02/16/2008
 
006 ( 30) OUTLET BOXES ARE NOT SECURED
BSMT THRU OUT
OPEN 02/16/2008 02/16/2008
 
007 ( 29) OUTLET BOXES ARE NOT COVERED
BSMT THRU OUT
OPEN 02/16/2008 02/16/2008
 
008 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
BSMT THRU OUT
OPEN 02/16/2008 02/16/2008
 
009 ( 17) DEFECTIVE SWITCHES ARE IN USE
BSMT THRU OUT
OPEN 02/16/2008 02/16/2008
 
010 ( 19) DEFECTIVE WIRING IS IN USE
BSMT THRU OUT
OPEN 02/16/2008 02/16/2008
 
011 ( 50) TEMPORARY OPEN WIRING IN CONTACT WITH PARTS OF THE BUILDING
BSMT THRU OUT
OPEN 02/16/2008 02/16/2008
 
012 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
NO GRD VISIBLE AT WATER MAIN OR 200A SER SW
OPEN 02/16/2008 02/16/2008