BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B418204
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 451 CLARKSON AVENUE BROOKLYN BIN: 3327711     Block: 4829   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 451 CLARKSON AV Census Tract:   808 Health Area:  5510
CELLAR & 1ST FLOOR Admin Area:   B - BROOKLYN Inspection Area:   G
BROOKLYN, NY 11203 Community Board:   309
DOB Cross Street(s):   NEW YORK AVENUE,    EAST 37 STREET
Status:   C - JOB IS SIGNED OFF 07/14/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/03/2016 1:58 PM
Application Entered:   10/03/2016 Job Start Date:   10/15/2016
Last Change:   07/14/2017 Job End Date:   05/15/2017
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     07/12/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012156 Licensee Name: DANIEL KELLY
Firm: 004120 Firm Name: MULTI-PHASE ELEC'L SVCS
Firm Phone: 646-430-8300  Firm Address: 1916-38 PARK AVE SUITE 406 NEW YORK NY 10037 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $712.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DANIEL GADIOMA
Owner Business Name: KINGS COUNTY HOSPITAL CTR
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  7  4 -150A, 3 - 200A
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  5  2 - #250 MCM, 3 - #3/0
D. Over 250 MCM  2  2 - #350 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL        16      340         
001                       
Buildings Total     19         340           
Total Units : 359 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/26/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: B418204
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/23/2017 06/26/2017 DNM V (67) (3)
INSPECTION COMMENTS: RECEPT OUTLETS NOT INSPECTED, CONTRACTOR NEED TO FILL OUT APP CORRECTLY FOR RECPT OUTLETS
 
(2) 07/12/2017 07/13/2017 DNM C R (45) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: B418204
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(CELLAR) CELLAR SWITCHES AND DIS-SWITCHES PLAQUES NOT PROVIDED 230.2
RSLV 06/23/2017 06/23/2017 07/12/2017
 
002 (999) OTHER
(CELLAR)CELLAR ALL SWITCHES AND DIS-SWITCHES 277/480 WARNING LABELS NOTPROVIDED 408.60
RSLV 06/23/2017 06/23/2017 07/12/2017
 
003 (999) OTHER
(CELLAR)CELLAR ALL ETN CPX 9000 CONTROLLERS GND NOT TERMINATED 250.112
RSLV 06/23/2017 06/23/2017 07/12/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.