| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 003) ALL ADJ. BREAKERS 400A NOT AS PER DRAWING |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 002 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 003) ART 310.16 OCP FOR 3AWG MAX 100A SECTION 2 |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 003 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (ALL FLOORS)ART 110.22 408.4 ALL SERVICE NOT LABELED AND ALL PANELS WITHOUTDIRECTIONS |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 004 |
( 61) |
INSTALLATION NOT IN COMPLIANCE WITH NYSECCC - SEE COMMENTS (ALL FLOORS) ART 110.16 ARC FLASH ALL SERVICE AND PANELS |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 005 |
( 61) |
INSTALLATION NOT IN COMPLIANCE WITH NYSECCC - SEE COMMENTS (ALL FLOORS) ART 240.12 FUSE COORDINATION NOT PROVIDED |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 006 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (BASEMENT) ART 250.64E 800A SS GEC RACEWAY NOT BONDED |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 007 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (BASEMENT) ART 250.92 2 PIPES FOR RETAIL SS NOT BONDED IN SEB |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 008 |
(192) |
CONDUCTORS ARE OVER FUSED AS PER TABLE 310.16 (BASEMENT) ART 310.16 SECTION 1 OCP FOR 1/0AWG MAX 130A |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 009 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (BASEMENT)ART 250.122 SIZE EGC 2500A FUSE 7 SET MC CABLE MIN 350MCM EGC FOREACH SET |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 010 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (BASEMENT) ART 645.15 DATA RACK NOT BONDED |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 011 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (BASEMENT) ART 250.94 INTERCOM GROUND BAR NOT PROVIDED FOR COMM ROOM |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 012 |
(220) |
DOUBLE LUGGING IN SERVICE SWITCH (BASEMENT) ART 110.14A EGC DOUBLE LUGGED IN ATS-C-LSP |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 013 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) 3 RETAIL 200A DISCONNECTS NOT ON DRAWING |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 014 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) ATS-C-LSP 1 SET 250MCM NOT AS PER DRAWING |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 015 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) FEEDER FP TO ROOF 1 SET 600MCM NOT AS PER DRAWING |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 016 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) TYPE FP TRANSFER SWITCH CONTROL BOX NOT ON DRAWING |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 017 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) SECTION 1 TYPE FUSE TR 200R NOT AS PER DRAWING |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 018 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) SECTION 2 100A FUSE NOT INSTALLED |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 019 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) SECTION 2 2 100A SWITCHES NOT INSTALLED |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 020 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) 1200A AND 800A FUSE TYPE KRP-C NOT AS PER DRAWING |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 021 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) 800A SS SIZE EGC 1/0AWG NOT AS PER DRAWING |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 022 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) SS 5 4 SET 500MCM NOT AS PER DRAWING |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 023 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) ONLY 4 SETS 500MCM FROM STREET NOT AS PER DRAWING |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 024 |
(277) |
BONDING JUMPER IS NOT PER ART 250.66 (BASEMENT) ART 250.66 SIZE GEC BONDING JUMPER SEB |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 025 |
(277) |
BONDING JUMPER IS NOT PER ART 250.66 (BASEMENT) ART 250.66 SIZE BONDING JUMPER SS 5 |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 026 |
(277) |
BONDING JUMPER IS NOT PER ART 250.66 (BASEMENT) ART 250.66 SIZE GEC FOR FA SS MIN 4AWG |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 027 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE (BASEMENT) ART 300.4G BUSHING ALL 3 RETAIL DISCONNECTS |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 028 |
( 55) |
CONDUCTORS SMALLER THAN 1/0 AWG HAVE BEEN RUN IN PARALLEL (BASEMENT)ART 310.4B 310.16 SECTION 1 USE 2 SET 6AWG FOR 200A FUSE |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 029 |
( 61) |
INSTALLATION NOT IN COMPLIANCE WITH NYSECCC - SEE COMMENTS (BASEMENT)ART 110.7 USE SHEETROCK SCREW FOR ALL COVERS IN SWITCH BOARD |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 030 |
( 61) |
INSTALLATION NOT IN COMPLIANCE WITH NYSECCC - SEE COMMENTS (BASEMENT) ART 230.70B SS NOT LABELED |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 031 |
( 61) |
INSTALLATION NOT IN COMPLIANCE WITH NYSECCC - SEE COMMENTS (BASEMENT) ART 700.8A SIGN FOR GENERATOR LOCATION AND TYPE |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 032 |
( 61) |
INSTALLATION NOT IN COMPLIANCE WITH NYSECCC - SEE COMMENTS (BASEMENT) ART 700.8B GEC FOR GENERATOR NOT IDENTIFIED |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 033 |
(340) |
RECEPTACLES NOT TAMPERPROOF (OPEN SPACE) ART 406.8B ALL OUTSIDE GFCI NOT WR |
RSLV |
06/14/2021 |
06/14/2021 |
12/10/2021 |
| |
| 034 |
(340) |
RECEPTACLES NOT TAMPERPROOF (OPEN SPACE) ART 406.8B NO COVER FOR OUTLET BOND STREET |
RSLV |
06/14/2021 |
06/14/2021 |
12/10/2021 |
| |
| 035 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (ROOF) ART 250.4B METAL PLATFORM NOT BONDED GENERATOR |
RSLV |
06/14/2021 |
06/14/2021 |
12/10/2021 |
| |
| 036 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (ROOF) SECTION 1 SIZE EGC FOR 2 SET 800A MIN 1/0AWG |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 037 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ROOF) FA SPLICE BOX UNDER GENERATOR NOT ON DRAWING |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 038 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ROOF) SECTION 1 FUSE 400A LPN-RK NOT AS PER DRAWING |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 039 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ROOF) SECTION 1 NO FUSES |
RSLV |
06/14/2021 |
06/14/2021 |
01/14/2022 |
| |
| 040 |
( 55) |
CONDUCTORS SMALLER THAN 1/0 AWG HAVE BEEN RUN IN PARALLEL (ROOF)ART 310.4B DB-R-GEN FOR PARALLEL RUN USE 1 SET IN PIPE AND SECONDSET IN MC CABLE |
RSLV |
06/14/2021 |
06/14/2021 |
12/10/2021 |
| |
| 041 |
(192) |
CONDUCTORS ARE OVER FUSED AS PER TABLE 310.16 (FLOOR: 004) ART 310.16 OCP 6AWG FEEDER FOR PANEL |
RSLV |
07/12/2021 |
07/12/2021 |
12/10/2021 |
| |
| 042 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (FLOOR: 004) ART 110.22A BOTH PANEL NOT LABELED |
RSLV |
07/12/2021 |
07/12/2021 |
12/10/2021 |
| |
| 043 |
( 61) |
INSTALLATION NOT IN COMPLIANCE WITH NYSECCC - SEE COMMENTS (FLOOR: 008) ART 110.7 WOODEN WALL SHEETROCK SCREW FOR OUTLETS |
RSLV |
07/12/2021 |
07/12/2021 |
12/10/2021 |
| |
| 044 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH (ALL FLOORS)ART 250.24A ALL ROOMS UNITS WHITE CONDUCTOR USE AS GROUND IN PANELON NEUTRAL BAR |
RSLV |
07/12/2021 |
07/12/2021 |
12/10/2021 |
| |
| 045 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (ALL FLOORS) ART 422.52 GFCI FOR WATER FOUNTAIN 5 AND 7 FLOOR |
RSLV |
07/12/2021 |
07/12/2021 |
12/10/2021 |
| |
| 046 |
(124) |
TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE (FLOOR: 001) ART 408.36 TAP WITHOUT OCP ALL LUTRON LIGHTING PANELS |
RSLV |
12/10/2021 |
12/10/2021 |
01/14/2022 |
| |
| 047 |
(192) |
CONDUCTORS ARE OVER FUSED AS PER TABLE 310.16 (FLOOR: 001)ART 310.16 PP-KP-N-6-4 3 AWG FUSED 200A 4 SWITCHES |
RSLV |
12/10/2021 |
12/10/2021 |
01/14/2022 |
| |
| 048 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (FLOOR: 001)ART 250.8A SCREW FOR GROUND BAR IN ALL KITCHEN SPLICE BOXES AFTERPANELS ABOVE CEILING |
RSLV |
12/10/2021 |
12/10/2021 |
01/14/2022 |
| |
| 049 |
(258) |
ENTRANCE TO WORKING SPACE IS OF INSUFFICIENT SIZE (FLOOR: 001) ART 110.26C LOCATION 1200A DP IN KITCHEN WITHOUT FENCE |
RSLV |
12/10/2021 |
12/10/2021 |
01/14/2022 |
| |
| 050 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (FLOOR: 002) ART 110.12A OPEN KO IN PP-2-N-1 |
RSLV |
12/10/2021 |
12/10/2021 |
01/14/2022 |
| |
| 051 |
( 61) |
INSTALLATION NOT IN COMPLIANCE WITH NYSECCC - SEE COMMENTS (FLOOR: 002) ART 406.8E FLOOR 50A OUTLET IN CONFERENCE ROOM |
RSLV |
12/10/2021 |
12/10/2021 |
01/14/2022 |
| |
| 052 |
( 36) |
CONDUCTORS ARE NOT PROPERLY COLOR CODED (FLOOR: 004)ART 250.119 GREEN CONDUCTOR USE AS HOT IN BOTH 60A PANELS |
RSLV |
12/10/2021 |
12/10/2021 |
01/14/2022 |
| |
| 053 |
(192) |
CONDUCTORS ARE OVER FUSED AS PER TABLE 310.16 (FLOOR: 014)ART 310.16 PB-R-N-1 10AWG FUSED 40A AND 70A 3 AWG FUSED 150A |
RSLV |
12/10/2021 |
12/10/2021 |
01/14/2022 |
| |
| 054 |
(200) |
LIGHT CONTROL NOT PROVIDED (ALL FLOORS)ART 210.70C LIGHTING NOT PROVIDED FOR ELECTRICAL CLOSETS |
RSLV |
12/10/2021 |
12/10/2021 |
01/14/2022 |
| |
| 055 |
( 36) |
CONDUCTORS ARE NOT PROPERLY COLOR CODED (ALL FLOORS)ART 200.7C WHITE CONDUCTOR USE AS HOT PP-C-EM WATER PUMP (WATERROOM) PB-R-N 1 AND ALL DISCONNECTS IN ROOF BOILER ROOM |
RSLV |
12/10/2021 |
12/10/2021 |
01/14/2022 |
| |
| 056 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE (ALL FLOORS)ART 300.4G BUSHINGS DB-C-EM DB-C-N2 400A DISCONNECT IN CELLARMECHANICAL ROOM 1200A DP IN KITCHEN |
RSLV |
12/10/2021 |
12/10/2021 |
01/14/2022 |
| |
| 057 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (ALL FLOORS)ART 210.8 GFCI PROTECTION IN CONFERENCE ROOM BAR AND COFFEE BAR INLOBBY |
RSLV |
12/10/2021 |
12/10/2021 |
01/14/2022 |
| |
| 058 |
( 61) |
INSTALLATION NOT IN COMPLIANCE WITH NYSECCC - SEE COMMENTS (ALL FLOORS)ART 110.2 SCREW FOR ALL METAL RACEWAY AND SPLICE BOXES CAN BE DAMAGEWIRE |
RSLV |
12/10/2021 |
12/10/2021 |
01/14/2022 |
| |
| 059 |
(136) |
GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS (BASEMENT) ART 250.50 SECOND WATER MAIN NOT BONDED TO COLLECTOR BAR |
RSLV |
12/10/2021 |
12/10/2021 |
01/14/2022 |
| |
| 060 |
(223) |
PROTECTION OF BRANCH CIRCUITS NOT INSTALLED AS PER CODE (BASEMENT) ART 240.4 OCP FOR WATER PUMP MAX 150A ADJUSTED 250A |
RSLV |
12/10/2021 |
12/10/2021 |
01/14/2022 |
| |
| 061 |
( 61) |
INSTALLATION NOT IN COMPLIANCE WITH NYSECCC - SEE COMMENTS (BASEMENT) ART 210.21B DRYER 120V CONNECTED TO 220V RECEPTACLE |
RSLV |
12/10/2021 |
12/10/2021 |
01/14/2022 |
| |
| 062 |
( 61) |
INSTALLATION NOT IN COMPLIANCE WITH NYSECCC - SEE COMMENTS (BASEMENT) ART 110.7 CONDUCTORS NOT SECURED IN PP-C-EM METAL RACEWAY |
RSLV |
12/10/2021 |
12/10/2021 |
01/14/2022 |
| |
| 063 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (ROOF) ART 250.4B WATER TOWER METAL PLATFORM NOT BONDED |
RSLV |
12/10/2021 |
12/10/2021 |
01/14/2022 |
| |
| 064 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (ROOF) ART 250.148 EGC NOT BONDED TO DISCONNECT WATER TOWER |
RSLV |
12/10/2021 |
12/10/2021 |
01/14/2022 |