Electrical Application Details for App #: M328402
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 244 7 AVENUE MANHATTAN BIN: 1014176     Block: 774   Lot: 7501
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 252 7 AV Census Tract:   91 Health Area:  5200
CELLAR Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   104
Special Place Name:   CHELSEA MERCANTILE
Related Job Number:    120958703
DOB Cross Street(s):   WEST 24 STREET,    WEST 25 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/13/2012 3:24 PM
Application Entered:   06/13/2012 Job Start Date:   06/18/2012
Last Change:   08/22/2025 Job End Date:   08/18/2012
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   SCHUSZTER, NORBET       On     11/10/2014      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 011355 Licensee Name: CARMINE L LIPPOLIS
Firm: 002775 Firm Name: LIPPOLIS ELECTRIC, INC.
Firm Phone: 718-892-4055  Firm Address: 4459 BRONX BOULEVARD BRONX NY 10470 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $408.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: CHELSEA MERCANTILE CONDO
Authorized Representative:  THOMAS LAZZARI
Relationship To Owner:   ASST SECRETARY


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  2  200 AMPS
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  800 AMPS
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  400 AMPS
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL                      45 
Buildings Total                        45 
Total Units : 45 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 11/24/2014
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  WIRE AND INSTALL CO-GENERATION SYSTEM

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: M328402
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/29/2013 12/05/2013 EDB V (60) (6) Y
INSPECTION COMMENTS: APLLICATION NOT PROPERLY FILED. NO ACCESS TO ELECTRICAL EQUIPMENT 5 T-FORMERS NOT ON FILE
 
(2) 11/10/2014 11/24/2014 NRS V Y (50) (2) Y
INSPECTION COMMENTS: ELECTRICIAN NOT FAMILIAR WITH INSTALLATION XFMRS NOT ON FILE

OBJECTION FOR APPLICATION #: M328402
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
GARAGE: SERVICE GFCI NOT WORKING BY CONDENSER UNIT AM. 110.2A
RSLV 11/29/2013 11/29/2013 11/10/2014
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
CEL 45 KVA T-FORMER: NOT PROPERLY GND. 250.112
OPEN 11/29/2013 11/10/2014
 
003 (999) OTHER
CEL PANEL AFTER T-FORMER: DOUBLE LUG ON POWER. 110.14A,3B
OPEN 11/29/2013 11/10/2014
 
004 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
CEL PANEL AFTER T-FORMER: NEUTRAL BONDED AFTER S.SW 250.24
OPEN 11/29/2013 11/10/2014
 
005 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
BSMT EL. RM: SERVICE OVER 1000 KVA. AM.110.2B,C
OPEN 11/29/2013 11/10/2014
 
006 (999) OTHER
BSMT 277/480V DISC. SW: CONCENTRIC K/O. 250.97
OPEN 11/29/2013 11/10/2014
 
007 (999) OTHER
BASE: BACK FED MAIN BREAKER NOT SECURED IN LIGHTING SB PANEL408.36D
OPEN 11/10/2014 11/10/2014
 
008 (999) OTHER
BASE: NO 480V WARNING. 408.60(C)
OPEN 11/10/2014 11/10/2014