Electrical Application Details for App #: M356576
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 148 BROADWAY MANHATTAN BIN: 1001087     Block: 64   Lot: 12
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 150 BROADWAY Census Tract:   15.02
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10038 Community Board:   101
DOB Cross Street(s):   LIBERTY STREET,    CORTLANDT STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   07/25/2014 Job Start Date:   07/10/2014
Last Change:   08/22/2025 Job End Date:   09/01/2014
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   RIVERA, F       On     12/17/2014      
Field Disp:   J - JOB IN PROGRESS
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  Y - PARTLY REMOVED

License #: 011831 Licensee Name: JAMES T GIORGIO, JR
Firm: 002393 Firm Name: B & G ELECL CONTR OF NY I
Firm Phone: 718-925-6900  Firm Address: 38-22 55 STREET WOODSIDE NY 11377 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,990.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   51818     Submittal #: 13A0282  
Owner / Occup: DANIEL MISHAEL
Owner Business Name: 150 BROADWAY NY ASSOC. LP
Authorized Representative:  DANIEL MISHAEL
Relationship To Owner:   PROPERTY MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  2  (1)2500,(1)2000,(1)1200
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  15  15 (4)#600KCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  (1)2500AMP DB
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 3
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 07/25/2014 Notice: 1 - FIRST NOTICE 09/19/2014
Power Issued: 07/25/2014 Response:  

Follow-Up:
Contractor's Comments:  JOB #4549

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: M356576
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/16/2014 09/19/2014 LBI A G (60) (3) Y
INSPECTION COMMENTS: SEE M354341
 
(2) 12/17/2014 12/22/2014 FRI J Y G (45) (0) Y
INSPECTION COMMENTS: NEW MDPS INSTALLED NOT AS PER ADV.BD DRAWINGS MUST SUBMIT REVISION - COPPER BUS OK

OBJECTION FOR APPLICATION #: M356576
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
BASEMENT BREAKERS AND COPPER BUS IN 1200A DISTRIBUTION BOARD. AM. 110.2B
OPEN 09/16/2014 12/17/2014
 
002 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BASEMENT FA CONTENT SVC RACEWAY NOT BONDED AT TROUGH. 250.92
RSLV 09/16/2014 09/16/2014 12/17/2014
 
003 (999) OTHER
BASEMENT GEC RACEWAY NOT CONTINUOUS AT GROUND ROD. 250.64E
RSLV 09/16/2014 09/16/2014 12/17/2014