Electrical Application Details for App #: M379781
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 433 EAST 52 STREET MANHATTAN BIN: 1040155     Block: 1364   Lot: 22
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 435 E 52ND ST Census Tract:   86.03 Health Area:  5000
4/5E Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10022 Community Board:   106
DOB Cross Street(s):    1 AVENUE,    DEAD END
Status:   C - JOB IS SIGNED OFF 10/11/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/30/2016 10:22 AM
Application Entered:   03/30/2016 Job Start Date:   04/01/2016
Last Change:   10/11/2018 Job End Date:   12/01/2016
Appointment Status:   
Last Inspection By:   DHANESHWAR BISSOON       On     10/11/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011197 Licensee Name: PHAT QUACH
Firm: 002600 Firm Name: MODERN TREND ELECL CONTRG
Firm Phone: 718-699-3300  Firm Address: 45-06 108TH STREET-2ND FL. CORP. CORONA NY 11368 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $201.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RESIDENCE ROSS
Owner Business Name: NA
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  3PHASE 225AMPS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004  48  36  38               
005  46  40  35               
Buildings Total 94  76  12  73                  
Total Units : 255 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 07/31/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: M379781
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/23/2018 03/26/2018 MJD V (40) (4)
INSPECTION COMMENTS: FAIL.
 
(2) 05/31/2018 06/01/2018 PHG V R (60) (8)
INSPECTION COMMENTS: CONTRACTOR TO FILE FOR HEATER AND MOTORS DID NOT INSPECT MOTORS/HEATER. MAIN RISER PULL BOX GLUED SHUT DID NOT INSPECT PULL BOX. LOAD CAL SELF CERTIFIABLE. PANEL AND FEEDER ADDED TO APP
 
(3) 07/30/2018 07/31/2018 DWB V X (40) (2)
INSPECTION COMMENTS: OBJECTION ISSUED,
 
(4) 08/14/2018 08/14/2018 TSO J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000012659
 
(5) 10/11/2018 10/11/2018 DWB C R (75) (0)
INSPECTION COMMENTS: CONTRACTOR FIX BONDING JUMPER IN SUB PANEL ON SIT, AS INSPECTED, NO OBJECTION.

OBJECTION FOR APPLICATION #: M379781
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 35) APPROVED OUTLETS HAVE NOT BEEN PROVIDED FOR AIR CONDITIONERS
(FLOOR: 005) WINDOW UNITS
RSLV 03/23/2018 03/23/2018 05/31/2018
 
002 (999) OTHER
(FLOOR: 005)ALL OUTLETS FOR WINDOW A/C UNITS NOT AFCI PROTECTED ART. 210.12
RSLV 03/23/2018 03/23/2018 05/31/2018
 
003 (999) OTHER
(FLOOR: 005)SURFACE MOUNT INCANDESCENT CLOSET LIGHT WITH IN 12" FROM STORAGEART. 410.16
RSLV 03/23/2018 03/23/2018 05/31/2018
 
004 (999) OTHER
(ALL FLOORS)BOX SET BACK IN COMBUSTIBLE MATERIAL (ALL OUTLETS IN WOOD BASEBOARD) ART. 314.20
RSLV 03/23/2018 03/23/2018 05/31/2018
 
005 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(FLOOR: 004) NO GROUND IN FMC MAIN FEEDER 250.122
RSLV 05/31/2018 05/31/2018 10/11/2018
 
006 (999) OTHER
(FLOOR: 004) PULL BOX GLUED SHUT IN CLOSET 314.29
RSLV 05/31/2018 05/31/2018 10/11/2018
 
007 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(FLOOR: 005) MAN MASTER CLOSET HANGING LOGHT NOT GROUNDED 250.122
RSLV 05/31/2018 05/31/2018 10/11/2018
 
008 (999) OTHER
(FLOOR: 005) PENDANT FIXTURE IN BATH RM TOO CLOSE TO TUB 410.10
RSLV 05/31/2018 05/31/2018 10/11/2018
 
009 (340) RECEPTACLES NOT TAMPERPROOF
(ALL FLOORS) AC NOT TAMPER 406.11
RSLV 05/31/2018 05/31/2018 10/11/2018
 
010 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS) AFCI NOT PROVIDED IN N NEEDED AREAS 210.12
RSLV 05/31/2018 05/31/2018 10/11/2018
 
011 (999) OTHER
(ALL FLOORS) EXPOSED BULB IN BOTH CLOTHES CLOSET 410.16
RSLV 05/31/2018 05/31/2018 10/11/2018
 
012 (999) OTHER
(ALL FLOORS) LOAD CALUATION NEEDED FROM 175 AMP FEED FOR DUPLEX APT
RSLV 05/31/2018 05/31/2018 08/14/2018
 
013 (999) OTHER
(FLOOR: 004) 250.66, GROUND CONDUCTOR NOT PROPER SIZE, FOR 200 AMP.
RSLV 07/30/2018 07/30/2018 10/11/2018
 
014 (999) OTHER
(ALL FLOORS)314.20, BOXES SET BACK WITH COMBUSTIBLE MATERIAL, WALL PAPER.
RSLV 07/30/2018 07/30/2018 10/11/2018