BIS Menu  |  Electrical Inspection Work Order  |  Plumb. Inspections  |  Property Profile  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M387683
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 692 BROADWAY MANHATTAN BIN: 1008529     Block: 531   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 692 BROADWAY Census Tract:   55.02 Health Area:  5700
CELLAR, 1ST FLOOR, MEZZANINE Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10012 Community Board:   102
Special Place Name:   AOL STUDIO
DOB Cross Street(s):   GREAT JONES STREET,    EAST 4 STREET
Status:   C - JOB IS SIGNED OFF 07/27/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/12/2016 2:30 PM
Application Entered:   10/12/2016 Job Start Date:   10/12/2016
Last Change:   07/27/2017 Job End Date:   10/12/2017
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     07/26/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012280 Licensee Name: CRAIG S DELDUCO
Firm: 004206 Firm Name: ALLRAN ELECTRIC OF NY LLC
Firm Phone: 212-269-5700  Firm Address: 120 BROADWAY, 36TH FLOOR NEW YORK NY 10005 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $587.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: VORNADO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  3#3
B. Over #2 to 1/0  5  3#3/0
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  6  5-200A, 1-100A
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    16      18  82             
001    14      18  72             
MZ1    19      95             
Buildings Total 49      40  249                
Total Units : 338 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/05/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: M387683
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/04/2017 04/05/2017 EDB V (115) (7)
INSPECTION COMMENTS: SEE ATTACHMENT.
 
(2) 05/04/2017 05/08/2017 FDY N (9) (0) Y
INSPECTION COMMENTS: CONTRACTOR SHOWED UP BUT NO ACCESS TO BUILDING.
 
(3) 06/12/2017 06/12/2017 STP J Y (40) (0)
INSPECTION COMMENTS: FAIL. PIPE SUPPORTS NEEDED TOUT.
 
(4) 07/26/2017 07/27/2017 CLC C R (30) (0)
INSPECTION COMMENTS: INSPECTION PASS

OBJECTION FOR APPLICATION #: M387683
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
(FLOOR: 001) WIRE WAY : OVER 30 CURRENT CONDUCTORS 376.22
RSLV 04/04/2017 04/04/2017 06/12/2017
 
002 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 002) OPEN WIRING AM. 110.2
RSLV 04/04/2017 04/04/2017 06/12/2017
 
003 ( 30) OUTLET BOXES ARE NOT SECURED
(FLOOR: 002) BOX NOT SECURED 314.23
RSLV 04/04/2017 04/04/2017 06/12/2017
 
004 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(FLOOR: 002) K/O MISSING 110.12
RSLV 04/04/2017 04/04/2017 06/12/2017
 
005 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(ALL FLOORS) MC CABLE NOT PROPERLY TERMINATED 330.40
RSLV 04/04/2017 04/04/2017 06/12/2017
 
006 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ALL FLOORS) OUTLET BOX(S) NOT FLASH W/COMBUSTIBLE 314.20,21
RSLV 04/04/2017 04/04/2017 06/12/2017
 
007 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(ALL FLOORS) EMT NOT SECURED 358.30
RSLV 04/04/2017 04/04/2017 07/26/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.