BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B388631
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 862 EAST 13 STREET BROOKLYN BIN: 3179214     Block: 6696   Lot: 32
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 862 E 13 ST Census Tract:   530 Health Area:  7310
862 EAST 13 Admin Area:   B - BROOKLYN Inspection Area:   K
BROOKLYN, NY 11230 Community Board:   314
Related Job Number:    320810495
DOB Cross Street(s):   DEAD END,    AVENUE I
Status:   C - JOB IS SIGNED OFF 01/25/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/12/2014 2:18 PM
Application Entered:   11/12/2014 Job Start Date:   11/12/2014
Last Change:   01/25/2017 Job End Date:   02/25/2015
Appointment Status:   
Last Inspection By:   BANYA, E       On     10/05/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012517 Licensee Name: SHABSE ROSENBERG
Firm: 004333 Firm Name: LIGHTEN UP ELEC'L SERVICE
Firm Phone: 718-704-0000  Firm Address: 1425 37TH STREET SUITE 611 CORP BROOKLYN NY 11218 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
T - TEMPORARY LIGHT & POWER
Total Fee:  $246.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  320810495
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOSHUA LANDMAN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  2  #2
C. Over 1/0 to 250 MCM  1  #3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  60 AMP 6/3 AWG
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  70 AMP 4/3 AWG
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    15  15    15  15             
001    25  25    18  25             
002    12  20    10  12             
Buildings Total 52  60    43  52                
Total Units : 207 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/12/2014 Notice: 1 - FIRST NOTICE 01/09/2016
Power Issued: 11/12/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: B388631
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/07/2016 01/09/2016 HRB V (48) (10)
INSPECTION COMMENTS: FAILED
 
(2) 01/19/2016 01/19/2016 HRB J Y (22) (0)
INSPECTION COMMENTS: NO ACCESS TO BASEMENT BEDROOM
 
(3) 08/11/2016 08/11/2016 EID N (27) (0) Y
INSPECTION COMMENTS: CONTRACTOR PRESENT, BUT HOMEOWNER NOT HOME. NO ACCESS.
 
(4) 10/05/2016 10/06/2016 EBA C R (45) (0)
INSPECTION COMMENTS: VIOLATIONS REMOVED

OBJECTION FOR APPLICATION #: B388631
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (111) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
(FLOOR: 001) FOR AC UNITS
RSLV 01/07/2016 01/07/2016 01/19/2016
 
002 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(ALL FLOORS) DIR IS WRONG
RSLV 01/07/2016 01/07/2016 01/19/2016
 
003 (109) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
(BASEMENT) GAS METER IN SAME SPACE WITH SERVICE SWITCH
RSLV 01/07/2016 01/07/2016 01/19/2016
 
004 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
(BASEMENT) ABOVE SERVICE SWITCH
RSLV 01/07/2016 01/07/2016 01/19/2016
 
005 ( 29) OUTLET BOXES ARE NOT COVERED
(BASEMENT) IN BOILER ROOM 5" BOX
RSLV 01/07/2016 01/07/2016 01/19/2016
 
006 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
(BASEMENT) NO LIGHT ABOVE SERVICE SWITCH
RSLV 01/07/2016 01/07/2016 01/19/2016
 
007 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT) NO WATER METER JUMPER
RSLV 01/07/2016 01/07/2016 01/19/2016
 
008 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(BASEMENT) NO AFCI ON ANYTHING IN BASEMENT
RSLV 01/07/2016 01/07/2016 10/05/2016
 
009 (999) OTHER
(BASEMENT) SERVICE RACEWAY NOT SEALED
RSLV 01/07/2016 01/07/2016 01/19/2016
 
010 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(OPEN SPACE) LIGHT ON SIDE OF HOUSE
RSLV 01/07/2016 01/07/2016 01/19/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.