NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 820 12 AVENUE MANHATTAN BIN: 1089709     Block: 1105   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 625 W 57TH ST Census Tract:   135 Health Area:  4500
GROUND Admin Area:   Z - UPPER MANHATTAN Inspection Area:   G
NEW YORK, NY 10019 Community Board:   104
DOB Cross Street(s):    11 AVENUE,    12 AVENUE
Status:   C - JOB IS SIGNED OFF 11/28/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/17/2017 10:41 AM
Application Entered:   04/17/2017 Job Start Date:   04/17/2017
Last Change:   11/28/2017 Job End Date:   04/17/2018
Appointment Status:   
Last Inspection By:   VINCENT CASTALDO       On     11/28/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011200 Licensee Name: CHRIS RICHEY
Firm: 002605 Firm Name: C.M. RICHEY ELEC'L CONTR
Firm Phone: 718-499-7417  Firm Address: 1001 SIXTH AVENUE SUITE 1102 NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,085.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   J - Theatre
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: DURST DEVELOPMENT, LLC
Authorized Representative:  JOSEPH HOBOT
Relationship To Owner:   AUTHORIZED SIGN.


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  6  (4SETS) 4#3, (2SETS) 4#10
B. Over #2 to 1/0  3  (3SETS) 4#4/0
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  (2SETS) 4#600
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  7  (1) 100A (6) 200A
D. 3 Phase Over 225 AMPS  1  (1) 800A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    240  310    55  240  22  90  12  225 
Buildings Total 240  310    55  240     90     12     225 
Total Units : 1172 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/17/2017 Notice: 1 - FIRST NOTICE 09/18/2017
Power Issued: 04/17/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: Z160202
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/16/2017 09/18/2017 MQY V (98) (4)
INSPECTION COMMENTS: INSPECTED PANELS, TRANSFORMERS, HVAC, & AND AN EMTPY THEATRE #7. (DID NOT INSPECT BAR, RESTAURANT, OTHER THEATRE ROOM AND BEHIND CONCESSION STANDS. TRANSFORMERS 600KCMILL SECONDARY CONDUCTORS TAPPED WITH 2/0 WIRES FOR 200 AMP PANELS THROUGH-OUT
 
(2) 11/28/2017 11/28/2017 VTC C R (21) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: Z160202
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT) 2/0 OVERFUSED AT 200A IN MAIN ELECTRIC ROOM T-OUT(310.16)
RSLV 09/16/2017 09/16/2017 11/28/2017
 
002 (999) OTHER
(BASEMENT)600 KCMILL SECONDARY OF BOTH 112.5 KVA TRANSFORMER IS TAPPED FORMULTIPLE PANELS (240.21)
RSLV 09/16/2017 09/16/2017 11/28/2017
 
003 (999) OTHER
(BASEMENT)110V RECEPTACLES IN COMMERCIAL KITCHEN NEEDS TO BE GFCI PROTECTED(210.8)
RSLV 09/16/2017 09/16/2017 11/28/2017
 
004 (999) OTHER
(BASEMENT)MECHANICAL ROOM ALL 277/480 DISCONNECTS NEEDS TO BE BONDED DUE TOCONCENTRIC KOS (250.97)
RSLV 09/16/2017 09/16/2017 11/28/2017