| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
3 - #2AWG |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
1 |
100A MBP 20CIRC |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
1 |
60 AMPS - 24 CTK |
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 19) |
DEFECTIVE WIRING IS IN USE (FLOOR: 010) WIRES STRIPPED AT EXCESSIVE LENGTH AT BREAKER TERMINATIONS |
RSLV |
02/11/2016 |
02/11/2016 |
11/09/2016 |
| |
| 002 |
( 30) |
OUTLET BOXES ARE NOT SECURED (FLOOR: 010) BOTH A/C RECE. BOXES |
RSLV |
02/11/2016 |
02/11/2016 |
11/09/2016 |
| |
| 003 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (FLOOR: 010) SHOWER PACK LIGHT |
RSLV |
02/11/2016 |
02/11/2016 |
11/09/2016 |
| |
| 004 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (FLOOR: 010) 208V 20A A/C RECE. PROTECTED AT 30A |
RSLV |
02/11/2016 |
02/11/2016 |
11/09/2016 |
| |
| 005 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (FLOOR: 010) AV QUAD RECE. IN CLOSET |
RSLV |
02/11/2016 |
02/11/2016 |
05/02/2016 |
| |
| 006 |
(999) |
OTHER (FLOOR: 010) COUNTER RECES. NOT SPACED AS PER 210.52 |
RSLV |
02/11/2016 |
02/11/2016 |
05/02/2016 |
| |
| 007 |
(999) |
OTHER (FLOOR: 010) INSTANT HOT RECE. BOX UNDER SINK SET TOO DEEP IN COMB. 210.14 |
RSLV |
02/11/2016 |
02/11/2016 |
05/02/2016 |
| |
| 008 |
( 21) |
CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED (FLOOR: 010) 10 CURRENT CONDUCTOR IN 1/2" PIPE |
RSLV |
05/02/2016 |
05/02/2016 |
11/09/2016 |
| |
| 009 |
( 9) |
SQ AREA OF SUM OF CONDUCTORS EXCEEDS SQ AREA FILL OF RACEWAY (FLOOR: 010) 1/2" PIPE W/10 # 12 AWG |
RSLV |
05/02/2016 |
05/02/2016 |
11/09/2016 |