Electrical Application Details for App #: M392085
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 56 LEONARD STREET MANHATTAN BIN: 1088646     Block: 176   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 56 LEONARD ST Census Tract:   33 Health Area:  7700
9TH, 9TH MEZZ, & 10TH FLOORS Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   101
Related Job Number:    104799648
DOB Cross Street(s):   WEST BROADWAY,    CHURCH STREET
Status:   C - JOB IS SIGNED OFF 04/17/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/10/2017 1:01 PM
Application Entered:   02/10/2017 Job Start Date:   02/10/2017
Last Change:   04/17/2017 Job End Date:   02/03/2018
Appointment Status:   
Last Inspection By:   SCHULER, THOMAS       On     04/12/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011575 Licensee Name: DANIEL LIVINGSTON
Firm: 003096 Firm Name: LIVINGSTON ELEC'L ASSOC.
Firm Phone: 718-969-2700  Firm Address: 162-20 77TH ROAD (INC.) FLUSHING NY 11366 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $162.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: KEYVAN KAZEMI
Owner Business Name: 56 LEONARD LLC
Authorized Representative:  RICHARD SAMUELSEN
Relationship To Owner:   PROJECT MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  1@#8, 1@#6
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
009    13    13  20         
MZ9                   
010    154    145             
Buildings Total 176    10  167     20           
Total Units : 381 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/28/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ELECTRICAL INSTALLATION FOR POOL ROOM AND ASSOCIATED EQUIPMENT.

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: M392085
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/03/2017 03/06/2017 EDB V (50) (4)
INSPECTION COMMENTS: JOB NOT COMPLETE. NOT FINAL. SEE ATTACHMENT.
 
(2) 03/28/2017 03/28/2017 STP V Y (50) (3)
INSPECTION COMMENTS: FAIL.
 
(3) 04/12/2017 04/12/2017 TUR C R (35) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: M392085
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 30) OUTLET BOXES ARE NOT SECURED
(FLOOR: 010) PULL/SPLICE BOX NOT SECURED BY POOL AREA 314
RSLV 03/03/2017 03/03/2017 04/12/2017
 
002 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(FLOOR: 010) JACUZZI SW. IN WET LOCATION 404.4
RSLV 03/03/2017 03/03/2017 03/28/2017
 
003 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ALL FLOORS) PVC IN USE AM. 352.10(I)
RSLV 03/03/2017 03/03/2017 04/12/2017
 
004 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ALL FLOORS) LFNC IN USE AM. 356.10
RSLV 03/03/2017 03/03/2017 03/28/2017
 
005 (999) OTHER
(FLOOR: 010) SPLICE BOX BURIED IN DIRT 314.29
RSLV 03/28/2017 03/28/2017 04/12/2017
 
006 (999) OTHER
(ALL FLOORS) PVC USED IN BUILDING EXCEEDING 3 FLOORS AMND 352.12
RSLV 03/28/2017 03/28/2017 04/12/2017
 
007 (999) OTHER
(ALL FLOORS) BONDING EXTENDS TO PANELBOARDS 680.26
RSLV 03/28/2017 03/28/2017 04/12/2017