| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
3 |
|
| D. 601 Up to 1200 AMPS |
2 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
71 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
|
| D. Over 250 MCM |
6 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
58 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
14 |
|
| D. 3 Phase Over 225 AMPS |
2 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
2 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER ROOF,DISCONNECT SWITCHES AT GENERATOR WITH THREE POLES TRANSFER SWITCHES NEUT BONDED TO ENCL ART.250.20D FPN #1 |
RSLV |
12/13/2011 |
12/13/2011 |
12/13/2011 |
| |
| 002 |
(999) |
OTHER ROOF,GROUNDING ELECTRODE CONDUCTOR ERMINATED AT GENERATOR DISC SW NEUT,ART 250.20D,ART 250.24 (A) (5) |
RSLV |
12/13/2011 |
12/13/2011 |
12/13/2011 |
| |
| 003 |
(999) |
OTHER ROOF,F.P. DISC SW. AT GENERATOR UNDER SOZE 75 HP MOTOR NYC AMEND 695.4 (B) (2) |
RSLV |
12/13/2011 |
12/13/2011 |
12/13/2011 |
| |
| 004 |
(999) |
OTHER ROOF,BASEMENT,CONTROL CONDUCTOR INSTALLED BBETWEEN F.P. TRANSFER SW& GENERATOR NOT FIRE RATED ART.695.14(F) |
RSLV |
12/13/2011 |
12/13/2011 |
12/13/2011 |
| |
| 005 |
(999) |
OTHER ROOF,FIRE PUMP AND FIRE ALARM DISC. SW. NOT MARK NYC AMEND.695.4 (B) (4) |
RSLV |
12/13/2011 |
12/13/2011 |
12/13/2011 |
| |
| 006 |
(999) |
OTHER ROOF: DISCONNECT SWITCHES AT GENERATOR WITH THREE POLES TRANSFERSWITCHES NEUTRAL BONDED TO ENCLOSURE.... - ART.250.20(D)(FPN #1) |
RSLV |
12/13/2011 |
12/13/2011 |
03/18/2012 |
| |
| 007 |
(999) |
OTHER ROOF: GROUNDING ELECTRODE CONDUCTOR TERMINATED AT GENERATOR DISC SWNEUTRAL...... - ART.250.20.D; ART.250.24(A)(5) |
RSLV |
12/13/2011 |
12/13/2011 |
03/18/2012 |
| |
| 008 |
(999) |
OTHER ROOF: F.P.DISC SW AT GENERATOR UNDER SIZE 75HP MOTOR....... -N.Y.C.AMEND 695.4(B)(2) |
RSLV |
12/13/2011 |
12/13/2011 |
03/18/2012 |
| |
| 009 |
(999) |
OTHER ROOF-BSMT: EMERG FDER FOR FIRE PUMP NOT FIRE RATED........ -N.Y.C.AMEND 695.6(B)(1) |
RSLV |
12/13/2011 |
12/13/2011 |
03/18/2012 |
| |
| 010 |
(999) |
OTHER ROOF-BSMT: CONTROL CONDUCTOR INSTALLED BETWEEN F.P.TRANSFORMER SW &GENERATOR NOT FIRE RATED....... - ART.695.14(F) |
RSLV |
12/13/2011 |
12/13/2011 |
03/18/2012 |
| |
| 011 |
(999) |
OTHER ROOF: FIRE PUMP AND FIRE ALARM DISC SW NOT MARK........ -N.Y.C.AMEND 695.4(B)(4) |
RSLV |
12/13/2011 |
12/13/2011 |
03/18/2012 |