Electrical Application Details for App #: M222367
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 135 FULTON STREET MANHATTAN BIN: 1001242     Block: 89   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 139 FULTON ST Census Tract:   15.01 Health Area:  7700
NONE Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10038 Community Board:   101
DOB Cross Street(s):   NASSAU STREET,    BROADWAY
Status:   C - JOB IS SIGNED OFF 10/17/2018
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   04/17/2003 Job Start Date:   03/24/2003
Last Change:   10/17/2018 Job End Date:   06/19/2003
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     10/16/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010275 Licensee Name: FRANK RAPPO
Firm: 001195 Firm Name: R & L SYSTEMS, INC.
Firm Phone: 718-397-5394  Firm Address: 37-20 56TH STREET WOODSIDE NY 11377 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $706.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: SMALL COMMERICAL PROPERTY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  4  
B. Each Additional 10 Floors Or Less  2  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/18/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: M222367
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/26/2018 01/29/2018 CBK V (60) (8)
INSPECTION COMMENTS: SEE OBJECTIONS DETAILS.
 
(2) 07/18/2018 07/18/2018 TOR V Y (60) (2)
INSPECTION COMMENTS: FAIL
 
(3) 10/16/2018 10/17/2018 CLC C R (60) (0)
INSPECTION COMMENTS: INSPECTION PASS

OBJECTION FOR APPLICATION #: M222367
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
(ALL FLOORS) GFCI NOT WIRED CORRECTLY ON CAR TOP AND PITS.
RSLV 01/26/2018 01/26/2018 10/16/2018
 
002 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(ALL FLOORS) CABLE NOT PROPERLY TERMINATED ON CAR TOP.
RSLV 01/26/2018 01/26/2018 07/18/2018
 
003 (999) OTHER
(BASEMENT) ONE PIT MISSING RECEPTACLE. 620.24(C)
RSLV 01/26/2018 01/26/2018 10/16/2018
 
004 (124) TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE
(ROOF) FEEDERS NOT PROPERLY TAPPED.
RSLV 01/26/2018 01/26/2018 07/18/2018
 
005 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(ROOF) OPEN KOS IN TROUGH AND DISCONNECTS.
RSLV 01/26/2018 01/26/2018 10/16/2018
 
006 (999) OTHER
(ROOF) FUSES DON'T MATCH IN DISCONNECTS. 110.3
RSLV 01/26/2018 01/26/2018 10/16/2018
 
007 (999) OTHER
(ROOF) NO CAR LIGHT DISCONNECT NOT PROVIDED. 620.53
RSLV 01/26/2018 01/26/2018 07/18/2018
 
008 (999) OTHER
(ROOF) 2 WIRES UNDER ONE LUG IN ELEVATOR DISC. 110.3
RSLV 01/26/2018 01/26/2018 07/18/2018
 
009 ( 19) DEFECTIVE WIRING IS IN USE
(ROOF) CAB LIGHT NEUTRALS NOT IN THE DISCONNECTS. T-OUT
RSLV 07/18/2018 07/18/2018 10/16/2018
 
010 ( 19) DEFECTIVE WIRING IS IN USE
(ROOF)GFCI IN THE PITS DEFECTIVE AND LIGHTS CONNECTED TO LOAD SIDE OFGFCIS T-OUT
RSLV 07/18/2018 07/18/2018 10/16/2018