| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
2 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
2 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
2 |
42 CIRCUIT MAIN CB |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 3) |
APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE BR. CKT WIRING BSMT + APT 6B, LIGHTS,SRVC SWCH, RECPTS, PNLS, FEEDS |
RSLV |
05/12/2007 |
05/12/2007 |
05/20/2008 |
| |
| 002 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER 200A SRVC SWCH NEUTRAL NOT BONDED TO ENCL |
RSLV |
05/12/2007 |
05/12/2007 |
05/20/2008 |
| |
| 003 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE NO FUSES 200A SRVC SWCH JUMPER WIRES |
RSLV |
05/12/2007 |
05/12/2007 |
05/20/2008 |
| |
| 004 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED 200A SRVC SWCH NEUTRAL NOT BONDED TERMINATED PROPERLY |
RSLV |
05/12/2007 |
05/12/2007 |
05/20/2008 |
| |
| 005 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) BSMT THROU-OUT |
RSLV |
05/12/2007 |
05/12/2007 |
05/20/2008 |
| |
| 006 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED BSMT THROU-OUT |
RSLV |
05/12/2007 |
05/12/2007 |
05/20/2008 |
| |
| 007 |
( 29) |
OUTLET BOXES ARE NOT COVERED BSMT THROU-OUT |
RSLV |
05/12/2007 |
05/12/2007 |
05/20/2008 |
| |
| 008 |
( 30) |
OUTLET BOXES ARE NOT SECURED BSMT THROU-OUT + 200A SRVC SWCH |
RSLV |
05/12/2007 |
05/12/2007 |
05/20/2008 |
| |
| 009 |
(999) |
OTHER APT 6B - COUNTERTOP RECEPTACLE WITH RAGE WOOD |
RSLV |
05/20/2008 |
05/20/2008 |
08/01/2011 |
| |
| 010 |
( 35) |
APPROVED OUTLETS HAVE NOT BEEN PROVIDED FOR AIR CONDITIONERS APT 6B - BEDROOM LIVING ROOM |
RSLV |
05/20/2008 |
05/20/2008 |
08/01/2011 |
| |
| 011 |
(999) |
OTHER A - APT 6B - NO TWO CIRCUIT PROVIDED FOR COUNTER TOP |
RSLV |
05/20/2008 |
05/20/2008 |
08/01/2011 |
| |
| 012 |
( 30) |
OUTLET BOXES ARE NOT SECURED APT 6B - BEDROOM RECEPTACLES |
RSLV |
05/20/2008 |
05/20/2008 |
08/01/2011 |
| |
| 013 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED BASEMENT - THRU-OUT |
RSLV |
05/20/2008 |
05/20/2008 |
08/01/2011 |
| |
| 014 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) THRU-OUT |
RSLV |
05/20/2008 |
05/20/2008 |
08/01/2011 |
| |
| 015 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED BASEMENT - AT WATER MAIN |
RSLV |
05/20/2008 |
05/20/2008 |
08/01/2011 |
| |
| 016 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER BASEMENT - COMB. PANEL S.E RCWY |
RSLV |
05/20/2008 |
05/20/2008 |
08/01/2011 |
| |
| 017 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER A - BASEMENT - SERVICE SWITCH IN |
RSLV |
05/20/2008 |
05/20/2008 |
08/01/2011 |
| |
| 018 |
(999) |
OTHER B - APT 6B PANEL NEUTRAL BAR IS BONDED AFTER SERVICE SWITCH |
RSLV |
05/20/2008 |
05/20/2008 |
08/01/2011 |