| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
5 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
1 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(109) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED 1FL: NO ACCESS TO GEC CONNECTION. 110.26 |
RSLV |
10/28/2014 |
10/28/2014 |
12/22/2014 |
| |
| 002 |
( 19) |
DEFECTIVE WIRING IS IN USE 1FL: SERV ENTER CONDUCTORS IN HALLOW SPACE. AM.230.43 |
RSLV |
10/28/2014 |
10/28/2014 |
12/22/2014 |
| |
| 003 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED 1FL: SERV.ENTER CONDUCTOR FOR FA S.S. UNDERSIZE. AM 230.31B |
RSLV |
10/28/2014 |
10/28/2014 |
12/22/2014 |
| |
| 004 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED BSMT: WATER MAIN UNDER SIZE (2 X 4/0 ON #2 AWG) T.250.66 |
RSLV |
10/28/2014 |
10/28/2014 |
12/22/2014 |
| |
| 005 |
(999) |
OTHER 1ST FL: PLP PANEL MULTIWIRE CKT NO GROUPED,NO SIMULT TRIP. 210.4 |
RSLV |
10/28/2014 |
10/28/2014 |
12/22/2014 |
| |
| 006 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) 1FL: EMT NOT PROPERLY SUPPORTED. 358.30 |
RSLV |
10/28/2014 |
10/28/2014 |
12/22/2014 |
| |
| 007 |
(311) |
FIXTURE NOT APPROVED FOR DAMP/WET LOCATION 2FL: BATHRM NOT APPROVED LIGHT FIXTURE. 410.10 |
RSLV |
10/28/2014 |
10/28/2014 |
12/22/2014 |
| |
| 008 |
(999) |
OTHER 2FL: CLOSET RECEPTACLE NOT FLUSH W/WOOD. 314.20,21 |
RSLV |
10/28/2014 |
10/28/2014 |
12/22/2014 |
| |
| 009 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED 3FL: LAUNDRY RECEPTACLE NOT A.F.C.I. PROTECTED(110V) 210.12 |
RSLV |
10/28/2014 |
10/28/2014 |
12/22/2014 |
| |
| 010 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED 2FL: OUTDOOR G.F.C.I.NOT WTR. 406.8A |
RSLV |
10/28/2014 |
10/28/2014 |
12/22/2014 |
| |
| 011 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED 2FL: OUTDOOR A/C UNIT NOT PROPERLY GND(LFMC). 250.112,118 |
RSLV |
10/28/2014 |
10/28/2014 |
12/22/2014 |
| |
| 012 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED 1FL: KITCHEN LIGHTS ON SMALL APPLIANCE CKT. 210.52B2 |
RSLV |
10/28/2014 |
10/28/2014 |
12/22/2014 |
| |
| 013 |
(999) |
OTHER 1FL: KITCHEN ISLAND RECEPTACLE MORE THAN6" OVER HANG. 210.52C5X |
RSLV |
10/28/2014 |
10/28/2014 |
12/22/2014 |
| |
| 014 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER FRONT: NO RECEPTACLE PROVIDED AT FRONT OF BUILDING UNIT. 210.52E |
RSLV |
10/28/2014 |
10/28/2014 |
12/22/2014 |