| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (ALL FLOORS) CELLAR: NO ARCH FLASH LABELS PNLS,METER,SWITCH.. 110.16 |
RSLV |
11/30/2015 |
11/30/2015 |
05/20/2016 |
| |
| 002 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (ALL FLOORS) CELLAR: EMT NOT SUPPORTED PROPERLY.. 358.30 |
RSLV |
11/30/2015 |
11/30/2015 |
05/20/2016 |
| |
| 003 |
(126) |
BASEMENT WATER MAIN GROUND NOT INSTALLED ON WATER MAIN (ALL FLOORS) CELLAR: NO WATER GROUND FOR SERVICE.. 250 |
RSLV |
11/30/2015 |
11/30/2015 |
07/29/2016 |
| |
| 004 |
(133) |
NO GROUND ROD: BASEMENT OR OUTSIDE (ALL FLOORS)CELLAR: NO SUPPLEMENTAL GROUND (NO WIRE OR ROD).. 250.52 |
RSLV |
11/30/2015 |
11/30/2015 |
07/29/2016 |
| |
| 005 |
(135) |
DEFECTIVE GROUND ROD IS IN USE (BASEMENT)250.52(A5) DEFECTIVE GROUND ROD IN USE FOUND CUT GROUND ROD ANDFILINGS ON FLOOR |
RSLV |
05/20/2016 |
05/20/2016 |
07/29/2016 |
| |
| 006 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (BASEMENT)250.24(C) SERVICE WATER GROUND AND SUPPLEMENTAL GROUND NOT PROPERLYINSTALLED THEY DID NOT INSTALL ON NEUTRAL THEY HIT FRAME |
RSLV |
05/20/2016 |
05/20/2016 |
07/29/2016 |