| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
2 |
#8 AND #6 FDR |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
2 |
MLO |
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(315) |
CONDUCTORS NOT PROPERLY IDENTIFIED (FLOOR: 004) USING WHITE #12 CONDUCTOR AS EGC FOR AC UNITS |
RSLV |
09/27/2016 |
09/27/2016 |
11/10/2016 |
| |
| 002 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (FLOOR: 004)NO ARC FAULT PROTECTION PROVIDED FOR SPIRAL STAIR CASE LIGHTING ONBOTH FLOORS |
RSLV |
09/27/2016 |
09/27/2016 |
11/10/2016 |
| |
| 003 |
( 61) |
INSTALLATION NOT IN COMPLIANCE WITH NYSECCC - SEE COMMENTS (FLOOR: 004)3RD AND 4TH FLOOR ON SAME SERVICE SWITCH SHOULD HAVE MEANS OF EGRESSFROM EACH APT |
RSLV |
09/27/2016 |
09/27/2016 |
11/10/2016 |
| |
| 004 |
(999) |
OTHER (FLOOR: 004)ALL OUTSIDE GFCI THROUGHOUT NOT WR/TR LISTED ART 406.8 A&B |
RSLV |
09/27/2016 |
09/27/2016 |
11/10/2016 |
| |
| 005 |
(999) |
OTHER (FLOOR: 004) TWIN BREAKERS NOT LISTED FOR PANEL BUS BAR |
RSLV |
09/27/2016 |
09/27/2016 |
11/10/2016 |
| |
| 006 |
(999) |
OTHER (FLOOR: 004)ALL BALCONIES WITH INTERIOR ACCESS REQUIRED GFCI RECEPATCLE ART210.52E3 |
RSLV |
09/27/2016 |
09/27/2016 |
11/10/2016 |
| |
| 007 |
(210) |
NO MEASURING OF ENERGY CONSUMPTION BY INDIVIDUAL DWELLING UNIT (ALL FLOORS)LOAD CALCULATION ITS REQUIRED FOR 3RD , 4TH AND 5TH FLOOR ON SAME 60AMP DISC/SW |
RSLV |
09/27/2016 |
09/27/2016 |
12/09/2016 |
| |
| 008 |
(109) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED (OPEN SPACE) FOR AC DISC/SW |
RSLV |
09/27/2016 |
09/27/2016 |
11/10/2016 |
| |
| 009 |
(999) |
OTHER (OPEN SPACE)NO DEDICATED CIRCUIT PROVIDE FOR AC CONDENSER USING ONE HOT LEG OF220V TO FEED GFCI ART 440.4 |
RSLV |
09/27/2016 |
09/27/2016 |
11/10/2016 |
| |
| 010 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (ROOF)FIBER OPTIC RACEWAY IS USED AS ELECTRICAL BRANCH CKT. RACEWAY TO &FROM SPLIT UNITTO SVC. DS AT WALL MOUNT UNIT |
RSLV |
11/10/2016 |
11/10/2016 |
12/09/2016 |