| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
1 SET # 2 CONDUCTOR |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
2 |
2-1 PHASE 20-1 POLE BRKRS |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 19) |
DEFECTIVE WIRING IS IN USE (ALL FLOORS) APTS. 1I,1H,BEDROOMS,OUTLETS WIRING DEFECTIVE |
RSLV |
03/25/2009 |
03/25/2009 |
06/28/2016 |
| |
| 002 |
( 19) |
DEFECTIVE WIRING IS IN USE (ALL FLOORS) APTS.1I,1H BATHS GFCI WIRING DEVECTIVE |
RSLV |
03/25/2009 |
03/25/2009 |
06/28/2016 |
| |
| 003 |
( 19) |
DEFECTIVE WIRING IS IN USE (ALL FLOORS) APTS.L 1I KITCHEN COUNTER GFCI WIRING DEFECTIVE |
RSLV |
03/25/2009 |
03/25/2009 |
06/28/2016 |
| |
| 004 |
( 6) |
FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION (ALL FLOORS) APT. 1I NEED LOAD CALCULATION FOR FEEDER #6 |
RSLV |
03/25/2009 |
03/25/2009 |
06/28/2016 |
| |
| 005 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE (ALL FLOORS) APT. 1I PANEL 10 WIRE FUSED AT 50AMPS |
RSLV |
03/25/2009 |
03/25/2009 |
06/28/2016 |
| |
| 006 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (ALL FLOORS) APT.1I FEEDER RACEWAY BEHIND STOVE IMPROPER CONN |
RSLV |
03/25/2009 |
03/25/2009 |
06/28/2016 |
| |
| 007 |
(999) |
OTHER (ALL FLOORS) APT 1H PANEL PHASE LEGS NOT BALANCED |
RSLV |
03/25/2009 |
03/25/2009 |
06/28/2016 |
| |
| 008 |
( 11) |
FEEDER CONDUCTORS ARE NOT OF PROPER SIZE (ALL FLOORS) APT 1H#6 FEEDER IMPROPER SIZE |
RSLV |
03/25/2009 |
03/25/2009 |
06/28/2016 |