Electrical Application Details for App #: Z121691
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 169 WEST 72 STREET MANHATTAN BIN: 1029916     Block: 1144   Lot: 1
   
Application Completed and Certified

Filed: 175 W 72 ST Census Tract:   157 Health Area:  4000
CELLAR AND 1ST FLOOR Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10023 Community Board:   107
DOB Cross Street(s):   COLUMBUS AVENUE,    AMSTERDAM AVENUE
Status:   C - JOB IS SIGNED OFF 07/25/2011
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/15/2009 2:51 PM
Application Entered:   05/15/2009 Job Start Date:   05/18/2009
Last Change:   07/25/2011 Job End Date:   07/15/2009
Appointment Status:   
Last Inspection By:   RIVERA, F       On     06/07/2011      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011998 Licensee Name: VADIM OMELIN
Firm: 003646 Firm Name: HESO ELECTRICAL INC
Firm Phone: 718-204-8568  Firm Address: 3418 NORTHERN BLVD, STE 4-5 LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $181.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   HANDBAG RETAIL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SING LAN LEE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200AMP 240VOLT 3PHASE
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  1 SET OF 4WIRE 3/O
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  150AMP 42 CIRCUIT
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    56  10               
Buildings Total 56  10                  
Total Units : 76 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 62 + New Meters 1 - Removed Meters 1 = Total Meters 62

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/15/2009 Notice: 1 - FIRST NOTICE 08/06/2010
Power Issued: 05/15/2009 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: Z121691
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/02/2010 02/08/2010 CLC A D (30) (3) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 08/02/2010 08/06/2010 CCH A R G (75) (9) Y
INSPECTION COMMENTS: NONE
 
(3) 06/07/2011 06/15/2011 FRI C R E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z121691
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: MORE THAN 6 SERVICE SW PROVIDED.....230.71
RSLV 02/02/2010 02/02/2010 08/02/2010
 
002 (999) OTHER
BSMT: SERVICE GND RACEWAY NOT CONTINUOUS....250.64(C)
RSLV 02/02/2010 02/02/2010 08/02/2010
 
003 (999) OTHER
BSMT: ROD NOT PROVIDED....25..52(A)(5)
RSLV 02/02/2010 02/02/2010 08/02/2010
 
004 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
A,SER SW #4 NEUTRAL NOT BONED
RSLV 08/02/2010 08/02/2010 06/07/2011
 
005 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
A,SER SW #3 KO MISSING TOP
RSLV 08/02/2010 08/02/2010 06/07/2011
 
006 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
END BOX KO MISSING
RSLV 08/02/2010 08/02/2010 06/07/2011
 
007 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
B,SPLICE BOX #6 SER SW KO MISSING
RSLV 08/02/2010 08/02/2010 06/07/2011
 
008 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
#6 RACEWAY NOT BONDED
RSLV 08/02/2010 08/02/2010 06/07/2011
 
009 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
B,#6 RACEWAY NOT BONDED
RSLV 08/02/2010 08/02/2010 06/07/2011
 
010 ( 8) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC)
#6 SER SW RACEWAY NOT PROPERLY SUPPORTED
RSLV 08/02/2010 08/02/2010 06/07/2011
 
011 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
C,#6 SER SW NEUTRAL NOT BONDED
RSLV 08/02/2010 08/02/2010 06/07/2011
 
012 (999) OTHER
#2 SER SW LINE & LOAD SAME RACEWAY 230.17
RSLV 08/02/2010 08/02/2010 06/07/2011