| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
200AMP 240VOLT 3PHASE |
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
1 SET OF 4WIRE 3/O |
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
150AMP 42 CIRCUIT |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER BSMT: MORE THAN 6 SERVICE SW PROVIDED.....230.71 |
RSLV |
02/02/2010 |
02/02/2010 |
08/02/2010 |
| |
| 002 |
(999) |
OTHER BSMT: SERVICE GND RACEWAY NOT CONTINUOUS....250.64(C) |
RSLV |
02/02/2010 |
02/02/2010 |
08/02/2010 |
| |
| 003 |
(999) |
OTHER BSMT: ROD NOT PROVIDED....25..52(A)(5) |
RSLV |
02/02/2010 |
02/02/2010 |
08/02/2010 |
| |
| 004 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER A,SER SW #4 NEUTRAL NOT BONED |
RSLV |
08/02/2010 |
08/02/2010 |
06/07/2011 |
| |
| 005 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX A,SER SW #3 KO MISSING TOP |
RSLV |
08/02/2010 |
08/02/2010 |
06/07/2011 |
| |
| 006 |
( 33) |
KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX END BOX KO MISSING |
RSLV |
08/02/2010 |
08/02/2010 |
06/07/2011 |
| |
| 007 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX B,SPLICE BOX #6 SER SW KO MISSING |
RSLV |
08/02/2010 |
08/02/2010 |
06/07/2011 |
| |
| 008 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE #6 RACEWAY NOT BONDED |
RSLV |
08/02/2010 |
08/02/2010 |
06/07/2011 |
| |
| 009 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER B,#6 RACEWAY NOT BONDED |
RSLV |
08/02/2010 |
08/02/2010 |
06/07/2011 |
| |
| 010 |
( 8) |
CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC) #6 SER SW RACEWAY NOT PROPERLY SUPPORTED |
RSLV |
08/02/2010 |
08/02/2010 |
06/07/2011 |
| |
| 011 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER C,#6 SER SW NEUTRAL NOT BONDED |
RSLV |
08/02/2010 |
08/02/2010 |
06/07/2011 |
| |
| 012 |
(999) |
OTHER #2 SER SW LINE & LOAD SAME RACEWAY 230.17 |
RSLV |
08/02/2010 |
08/02/2010 |
06/07/2011 |