Electrical Application Details for App #: A323637
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 53-30 61 STREET QUEENS BIN: 4054296     Block: 2365   Lot: 77
   
Application Completed and Certified

Filed: 53-30 61 ST Census Tract:   515 Health Area:  1700
2ND FLOOR Admin Area:   A - QUEENS Inspection Area:   G
QUEENS, NY 11378 Community Board:   405
DOB Cross Street(s):    53 DRIVE,    62 STREET
Status:   C - JOB IS SIGNED OFF 11/24/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/08/2014 2:37 PM
Application Entered:   01/08/2014 Job Start Date:   01/08/2014
Last Change:   11/24/2014 Job End Date:   01/08/2015
Appointment Status:   
Last Inspection By:   BASDEO, C       On     10/28/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011396 Licensee Name: SPIRO VALENTIS
Firm: 002831 Firm Name: VALENTIS ELECTRIC, INC.
Firm Phone: 718-726-0072  Firm Address: 32-21 58TH STREET WOODSIDE NY 11377 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $86.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GABRIELA NATKANIEC
Owner Business Name: SAME
Authorized Representative:  GABRIELA NATKANIEC
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  #3 THHN
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  24 CIRCUITS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002    40  22  12               
Buildings Total 40  22  12                  
Total Units : 76 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 09/29/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WIRING 2ND FLOOR

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: A323637
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/22/2014 09/29/2014 TSO A (30) (6) Y
INSPECTION COMMENTS: OBJECTIONS
 
(2) 10/28/2014 11/05/2014 COB C R (35) (0) Y
INSPECTION COMMENTS: CERTIFICATE

OBJECTION FOR APPLICATION #: A323637
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
2ND FLOOR GFCI BREAKERS USED WHERE AFCI NEEDED 210.12
RSLV 09/22/2014 09/22/2014 10/28/2014
 
002 (999) OTHER
2ND FLOOR AFCI NOT COMBO TYPE 210.12
RSLV 09/22/2014 09/22/2014 10/28/2014
 
003 (999) OTHER
2ND FLOOR NO W/R T/R ON DECK 406.8
RSLV 09/22/2014 09/22/2014 10/28/2014
 
004 (999) OTHER
2ND FLOOR NO IN USE COVER DECK 406.8
RSLV 09/22/2014 09/22/2014 10/28/2014
 
005 (999) OTHER
2ND FLOOR FEEDER TO UPSTAIRS PANEL UNDERSIZED 72A STEAM UNIT ONWITH WHOLE 2ND FLOOR 220.40
RSLV 09/22/2014 09/22/2014 10/28/2014
 
006 (999) OTHER
2ND FLOOR NO A/C CIRCUIT ROOM TOP STAIRS 210.52A
RSLV 09/22/2014 09/22/2014 10/28/2014