BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B385995
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 173 WATER STREET BROOKLYN BIN: 3411556     Block: 30   Lot: 102
   
Application Completed and Certified

Filed: 173 WATER ST Census Tract:   21 Health Area:  1000
ENTIRE Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
Related Job Number:    320514617
DOB Cross Street(s):   PEARL STREET,    JAY STREET
Status:   C - JOB IS SIGNED OFF 10/16/2015 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/11/2014 12:07 PM
Application Entered:   09/11/2014 Job Start Date:   09/12/2014
Last Change:   10/16/2015 Job End Date:   09/11/2015
Appointment Status:   
Last Inspection By:   GLENN BALZARANO       On     06/17/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010548 Licensee Name: ANTHONY REALE
Firm: 003631 Firm Name: AA REALE ELECTRIC INC
Firm Phone: 718-499-8731  Firm Address: 4223 1ST AVENUE BROOKLYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $121.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JARED R DELLAVALLE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  3/0
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    10               
002    10               
003    10               
004             
Buildings Total 18  37    18  18              
Total Units : 94 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/11/2014 Notice: 1 - FIRST NOTICE 05/26/2015
Power Issued: 09/11/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: B385995
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/30/2015 05/07/2015 DAH A G (60) (9) Y
INSPECTION COMMENTS: N
 
(2) 05/21/2015 05/26/2015 DEX A Y G (40) (1) Y
INSPECTION COMMENTS: NEED TO PUT PANELS FOR DOORS ON ROOF FOR AC UNIT
 
(3) 06/17/2015 06/24/2015 GBZ C R E (25) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: B385995
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
SUPPLIMENTAL GROUND NOT PROVIDED ARTICLE 210
RSLV 04/30/2015 05/21/2015 06/17/2015
 
002 (999) OTHER
GND FL JUMPER NOT PROVIDED AT WTR MTR ARTICLE 250.53 (D)
RSLV 04/30/2015 05/21/2015 06/17/2015
 
003 (999) OTHER
DEVICES SET BACK MORE THAN 1/4 ARTICLE 314.20
RSLV 04/30/2015 04/30/2015 05/21/2015
 
004 (999) OTHER
RECEPTICLES INSTALLED BEHIND COUNTER# SURFACE ARTICLE 406.4 (E)
RSLV 04/30/2015 04/30/2015 05/21/2015
 
005 (999) OTHER
RECEPTICLES INSTALLED FACING UP ARTICLE 406.4 (E)
RSLV 04/30/2015 04/30/2015 05/21/2015
 
006 (999) OTHER
DS NOT PROVIDED AT HVAC UNIT ARTICLE 30.74
RSLV 04/30/2015 04/30/2015 05/21/2015
 
007 (999) OTHER
NOT APPLIED TO RACEWAY ABOVE
RSLV 04/30/2015 04/30/2015 05/21/2015
 
008 (999) OTHER
SVC PNL MORE THAN 3 CONDUCTORS TABLE 310. TABLE C1
RSLV 04/30/2015 04/30/2015 05/21/2015
 
009 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ECG IN DS FOR HVAC IS NOT BONDED IN SWITCH
RSLV 04/30/2015 04/30/2015 05/21/2015
 
010 ( 37) MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED
2ND FL-OVEN IN KITCHEN NO DISSCONNECT WITH INSIGHT
RSLV 05/21/2015 05/21/2015 06/17/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back