Electrical Application Details for App #: M346605
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 1200 FDR DRIVE MANHATTAN BIN: 1088433     Block: 962   Lot: 80
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1200 FDR DR Census Tract:   86
2 FLOOR Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10016 Community Board:   106
DOB Cross Street(s):   EAST 30 STREET,    EAST 34 STREET
Status:   C - JOB IS SIGNED OFF 07/13/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/21/2013 9:27 AM
Application Entered:   10/21/2013 Job Start Date:   10/21/2013
Last Change:   07/13/2017 Job End Date:   10/21/2014
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     06/28/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012213 Licensee Name: LEONARD HARRINGTON
Firm: 003932 Firm Name: ALLAN/BRITE-WAY ELEC'L CO
Firm Phone: 646-694-8914  Firm Address: 228 EAST 45TH STREET, 9TH FL NEW YORK NY 10017 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
012031 ALVAREZ, LOUIS 003932 ALLAN/BRITE-WAY ELEC'L CO

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $1,131.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOSEPH COUGHLIN
Owner Business Name: NYUMC R.E.DEV.
Authorized Representative:  TY CLANTON
Relationship To Owner:   OWNERS REP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  
B. Over #2 to 1/0  1  
C. Over 1/0 to 250 MCM  2  
D. Over 250 MCM  2  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  4  
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002    290  825    95  455          410 
Buildings Total 290  825    95  455               410 
Total Units : 2075 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/06/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  AB JOB NO. NY-13161-00

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: M346605
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/10/2015 02/18/2015 DNM C (60) (0) Y
INSPECTION COMMENTS: SERVICE DONE BY OTHER. ELECTRICIAN PICKED UP BRANCH CIRCUITS
 
(2) 03/30/2015 04/06/2015 DNM V (45) (4) Y
INSPECTION COMMENTS: GENERATORS HAVE TO BE TESTED FOR NEXT INSPECTION
 
(3) 06/14/2017 06/14/2017 EDB N (55) (0) Y
INSPECTION COMMENTS: CALL CONTRACTOR, NEED TO RESCHEDULE. NO SHOW.
 
(4) 06/28/2017 06/28/2017 TOR C R (70) (0)
INSPECTION COMMENTS: CONTRACTOR DID NOT INSTALL SECOND LINE OF FUSES FROM 4000 AMP SERVICE (JOB PREVIOUSLY DONE BY APP M340076

OBJECTION FOR APPLICATION #: M346605
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)HOSPITAL: ADVISORY BOARD DRAWING FOR 1000 KVA SERVICE IS NOT SUBMIT-TED FOR APPROVAL.. 110.2
RSLV 03/30/2015 03/30/2015 06/28/2017
 
002 (999) OTHER
(ALL FLOORS)A) HOSPITAL: GROUNDING ELECTRODE CONDUCTOR NOT CONTINUOUSART.250.64
RSLV 03/30/2015 03/30/2015 06/28/2017
 
003 (999) OTHER
(ALL FLOORS)B) HOSPITAL: NEUTRAL DISCONNECT LINK IS NOT PROVIDED FOR 3 4000 AMPPARALLELING SWITCH GEAR.. ART.408.3
RSLV 03/30/2015 03/30/2015 06/28/2017
 
004 (999) OTHER
(ALL FLOORS)C) HOPITAL: 3 GENERATORS ARE NOT LISTED FOR THE U.S.. ART.110.2
RSLV 03/30/2015 03/30/2015 06/28/2017