BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M372019
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 139 LUDLOW STREET MANHATTAN BIN: 1005359     Block: 411   Lot: 29
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 139 LUDLOW ST Census Tract:   30.01 Health Area:  6600
BASE-ROOF Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10002 Community Board:   103
DOB Cross Street(s):   RIVINGTON STREET,    STANTON STREET
Status:   C - JOB IS SIGNED OFF 12/28/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/04/2015 8:04 AM
Application Entered:   09/04/2015 Job Start Date:   09/04/2015
Last Change:   12/28/2016 Job End Date:   08/01/2016
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     12/27/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010698 Licensee Name: ERNEST JOCHEN
Firm: 001918 Firm Name: BIG SHOT ELECTRIC CORP.
Firm Phone: 718-292-0033  Firm Address: 710 EAST 135TH STREET BRONX NY 10454 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,470.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   CLUB
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GILES COOPER
Owner Business Name: 139 LUDLOW ACQUISITIONS L
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  1  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  6  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  7  
D. 3 Phase Over 225 AMPS  3  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 1
Existing Meters 1 + New Meters 2 - Removed Meters 1 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/04/2015 Notice: 1 - FIRST NOTICE 08/04/2016
Power Issued: 09/04/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: M372019
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/02/2016 08/04/2016 PHG V (90) (2)
INSPECTION COMMENTS: CONTRACTOR TO FILE FOR FA SERVICE SW ALL FEEDERS AND MATERIAL LIFT DID NOT INSPECT MATERIAL LIFT
 
(2) 12/27/2016 12/28/2016 TOR C R (30) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M372019
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT) FIRE SERVICE ENTRANCE NO BOND 250.92
RSLV 08/02/2016 08/02/2016 12/27/2016
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT) NO GRND OR SUPPLEMENTAL FOR FIRE SERVICE 250.64
RSLV 08/02/2016 08/02/2016 12/27/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back