BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B302966
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 209 A ECKFORD STREET BROOKLYN BIN: 3065684     Block: 2621   Lot: 24
   
Application Completed and Certified

Filed: 209 1/2 ECKFORD ST Census Tract:   573 Health Area:  0200
B,1,2 Admin Area:   B - BROOKLYN Inspection Area:   A
BROOKLYN, NY 11222 Community Board:   301
DOB Cross Street(s):   NORMAN AVENUE,    MESEROLE AVENUE
Status:   C - JOB IS SIGNED OFF 09/23/2008
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   04/09/2008 Job Start Date:   05/01/2008
Last Change:   09/23/2008 Job End Date:   12/01/2009
Appointment Status:   
Last Inspection By:   COHN, MARTIN       On     08/29/2008      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012226 Licensee Name: SLAWOMIR BARNAS
Firm: 003950 Firm Name: ELECTRA ELECTRICAL, INC
Firm Phone: 212-340-1949  Firm Address: 244 5TH AVENUE, STE B283 NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $269.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: KRZYSZTOF ROSTEK
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  3  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  4  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  2  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 58  68  36  58              
Total Units : 230 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 3 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/09/2008 Notice: C - CALL TO OFFICE 08/18/2008
Power Issued: 04/09/2008 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: B302966
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/08/2008 07/14/2008 CLC A E (45) (5) Y
INSPECTION COMMENTS: N
 
(2) 08/05/2008 08/18/2008 MC2 H X G (45) (0) Y
INSPECTION COMMENTS: VIOLATIONS REMAIN
 
(3) 08/29/2008 08/29/2008 MC2 C R E (50) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B302966
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
1ST FLOOR SERVICE ENTRANCE RACEWAYS
RSLV 07/08/2008 08/05/2008 08/29/2008
 
002 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
1ST FLOOR SERVICE ENTRANCE RACEWAYS
RSLV 07/08/2008 08/05/2008 08/29/2008
 
003 (999) OTHER
1ST FLOOR SERVICE ENTRANCE LB NOT ACCESSIBLE 300.15A
RSLV 07/08/2008 08/05/2008 08/29/2008
 
004 (999) OTHER
1ST FLOOR SER ENT IS IN THE HOLLOW FRAME OF THE BLDG 230.43EAMEND
RSLV 07/08/2008 08/05/2008 08/29/2008
 
005 ( 28) ELECTRICAL MATERIAL USED FOR LUMINAIRES HAS NOT BEEN APPROVED
3RD FLOOR APTS BEDROOM SHOWER LIGHTS NOT APPROVED FOR DAMP LOCATION
RSLV 07/08/2008 08/05/2008 08/29/2008



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back