BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M320945
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 90 PRINCE STREET MANHATTAN BIN: 1007586     Block: 498   Lot: 7501
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 90 PRINCE ST Census Tract:   49 Health Area:  6800
ROOF Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
Special Place Name:   PAULA RYBACZYK
DOB Cross Street(s):   BROADWAY,    MERCER STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/19/2011 10:28 PM
Application Entered:   11/19/2011 Job Start Date:   11/23/2011
Last Change:   08/22/2025 Job End Date:   11/30/2011
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   CHARLES COURTNEY       On     05/07/2012      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  

License #: 009365 Licensee Name: MICHAEL SCHONDORF
Firm: 000995 Firm Name: MICHAEL SCHONDORF, INC
Firm Phone: 212-244-4312  Firm Address: 545 WEST 45TH STREET..6F NEW YORK NY 10036 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $58.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PAULA RYBACZYK
Owner Business Name: NEW BEDFORD MANAGEMENT
Authorized Representative:  PAULA RYBACZYK
Relationship To Owner:   MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  ON ROOF
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                 
ROF      15         
Buildings Total      15           
Total Units : 23 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 05/21/2012
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  INSTALLATION OF "FEEDER" ONLY FOR ELEVATOR

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: M320945
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/07/2012 05/21/2012 CCH A (60) (1) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS

OBJECTION FOR APPLICATION #: M320945
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: NEED LOAD CALCULATION....... - 220.11 13FOR FEEDERS TO ROOF
OPEN 05/07/2012 05/07/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back