Electrical Application Details for App #: M326390
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 25 BROAD STREET MANHATTAN BIN: 1000824     Block: 25   Lot: 19
   
Application Completed and Certified

Filed: 25 BROAD ST Census Tract:   9 Health Area:  7700
* Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10004 Community Board:   101
DOB Cross Street(s):   EXCHANGE PLACE,    BEAVER STREET
Status:   C - JOB IS SIGNED OFF 06/03/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/25/2012 4:24 PM
Application Entered:   04/25/2012 Job Start Date:   05/01/2012
Last Change:   06/03/2013 Job End Date:   05/01/2013
Appointment Status:   
Last Inspection By:   HUGH MCKESSEY       On     05/31/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011889 Licensee Name: MICHAEL L KAUFMAN
Firm: 003519 Firm Name: ESSENTIAL ELECTRIC CORP
Firm Phone: 212-725-1098  Firm Address: 32 EAST 31ST STREET-8TH FL NEW YORK NY 10016 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: THOMAS GAGLIANO
Owner Business Name: 25 BROAD ST LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  3 STOP 2000 LB ELEVATOR
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/17/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ELEVATOR INSTALLATION ONLY

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: M326390
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/08/2013 03/22/2013 DAH N (15) (0) Y
INSPECTION COMMENTS: *NO SHOW*
 
(2) 04/08/2013 04/17/2013 LBI A (35) (2) Y
INSPECTION COMMENTS: *#1P47205* **SEE OBJECTIONS
 
(3) 05/31/2013 06/03/2013 HMC C R (20) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M326390
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (101) CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED
MOTOR ROOM: HYDAC OIL COOLER REQUIRES FIELD EVALUATION FOR US LIST-ING........ - AMEND 110.2
RSLV 04/08/2013 04/08/2013 05/31/2013
 
002 (192) CONDUCTORS ARE OVER FUSED AS PER TABLE 310.16
MOTOR ROOM: OIL COOLER #12 WIRES ON 30A FUSE..... - 240.4
RSLV 04/08/2013 04/08/2013 05/31/2013