BIS Menu  |  Electrical Inspection Work Order  |  Elev. Device Details  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z136608
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 328 WEST 96 STREET MANHATTAN BIN: 1034193     Block: 1253   Lot: 90
   
Application Completed and Certified

Filed: 328 W 96 ST Census Tract:   183 Health Area:  3110
APT. 3D Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10025 Community Board:   107
DOB Cross Street(s):   WEST END AVENUE,    RIVERSIDE DRIVE
Status:   C - JOB IS SIGNED OFF 06/27/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/05/2012 1:04 PM
Application Entered:   09/05/2012 Job Start Date:   09/05/2012
Last Change:   06/27/2013 Job End Date:   11/15/2012
Appointment Status:   
Last Inspection By:   KEMPF, JOHN       On     06/19/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011127 Licensee Name: ANTHONY SARACENI
Firm: 002504 Firm Name: DELTA PHASE ELEC'L CORP.
Firm Phone: 718-963-9000  Firm Address: 137 29TH STREET BROOKYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $89.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 328 WEST 96TH ST OWNERS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  3 - #4'S
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  20 CIRCUITS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003  3D  24  26    14  24             
Buildings Total 24  26    14  24                
Total Units : 88 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 05/09/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: Z136608
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/29/2013 05/09/2013 JKF A (45) (6) Y
INSPECTION COMMENTS: **SEE OBJECTIONS
 
(2) 06/19/2013 06/27/2013 JKF C R (40) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z136608
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
KITCHEN: DISHWASHER & COUNTER CIRCUIT SHARED
RSLV 04/29/2013 04/29/2013 06/19/2013
 
002 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
KITCHEN: CABINET LIGHTS
RSLV 04/29/2013 04/29/2013 06/19/2013
 
003 ( 19) DEFECTIVE WIRING IS IN USE
KITCHEN: MICROWAVE BOX SET BACK IN WOOD..... - 314.20
RSLV 04/29/2013 04/29/2013 06/19/2013
 
004 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
KITCHEN: LIGHTING
RSLV 04/29/2013 04/29/2013 06/19/2013
 
005 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
BATH: LIGHTING
RSLV 04/29/2013 04/29/2013 06/19/2013
 
006 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
PANEL
RSLV 04/29/2013 04/29/2013 06/19/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order  |  Elev. Device Details  |  Back