BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M338077
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 155 EAST 81 STREET MANHATTAN BIN: 1047565     Block: 1510   Lot: 27
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 157 E 81 ST Census Tract:   140 Health Area:  3600
5TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10028 Community Board:   108
DOB Cross Street(s):   LEXINGTON AVENUE,    3 AVENUE
Status:   C - JOB IS SIGNED OFF 02/15/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/18/2013 9:23 AM
Application Entered:   03/18/2013 Job Start Date:   03/19/2013
Last Change:   02/15/2017 Job End Date:   12/30/2013
Appointment Status:   
Last Inspection By:   URIM SYLA       On     01/04/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010481 Licensee Name: VITO MARINELLI
Firm: 001622 Firm Name: V-MAR ELECTRIC LTD.
Firm Phone: 718-782-9700  Firm Address: 408 GRAND STREET BROOKLYN NY 11211 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $209.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LAURIE KEFALIDIS
Owner Business Name: CARLTON HOUSE CORP
Authorized Representative:  LAURIE KAFALIDIS
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200A, S.S.
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  1 3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
005  53  45    30  53         
Buildings Total 53  45    30  53              
Total Units : 188 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 10/11/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REWIRE COMPLETE APARTMENT AS PER NEW CODE

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: M338077
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/14/2014 10/21/2014 EID A (60) (9) Y
INSPECTION COMMENTS: NONE
 
(2) 10/11/2016 10/11/2016 GYM H X (75) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW.
 
(3) 12/06/2016 12/07/2016 BMP N (30) (0) Y
INSPECTION COMMENTS: NO ACCESS.
 
(4) 01/04/2017 01/05/2017 UMS C R (35) (0)
INSPECTION COMMENTS: OBJECTIONS CLEARED

OBJECTION FOR APPLICATION #: M338077
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ALL FLOORS) PNL 2: #12 FUSED AT 30A OCP FOR A/C. 240.3
RSLV 10/14/2014 10/14/2014 01/04/2017
 
002 (999) OTHER
(ALL FLOORS) 5TH FL: DINING RM CHAND.NOT GND. 250.8
RSLV 10/14/2014 10/14/2014 01/04/2017
 
003 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS) PNL 1: A.F.C.I. PROT NOT PROVIDED. 210.12(B)
RSLV 10/14/2014 10/14/2014 01/04/2017
 
004 ( 19) DEFECTIVE WIRING IS IN USE
(ALL FLOORS) PNL 1: #14 COND USED/FUSED AT 20A. 240.3
RSLV 10/14/2014 10/14/2014 01/04/2017
 
005 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(ALL FLOORS) PNL 1: NEUTRAL BND IN PNL. 250.24(A5)
RSLV 10/14/2014 10/14/2014 01/04/2017
 
006 (999) OTHER
(ALL FLOORS) OUTSIDE: A/C UNIT NOT FUSED AS PER MAN SPEC. 110.2
RSLV 10/14/2014 10/14/2014 01/04/2017
 
007 (999) OTHER
(ALL FLOORS) OUTSIDE: DEL LUG ON EGC IN A/C DISC. 110.14(A)
RSLV 10/14/2014 10/14/2014 01/04/2017
 
008 (999) OTHER
(ALL FLOORS) T-OUT: SCONCES NOT PROPERLY GND. 250.8
RSLV 10/14/2014 10/14/2014 01/04/2017
 
009 (307) NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT
(ALL FLOORS)OUTSIDE: SERVICE RECEP/G.F.C.I.NOT PROVIDED FOR A/C UNIT. 210.63
RSLV 10/14/2014 10/14/2014 01/04/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.