BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M340562
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 233 ELIZABETH STREET MANHATTAN BIN: 1007908     Block: 508   Lot: 44
   
Application Completed and Certified

Filed: 235 ELIZABETH ST Census Tract:   43 Health Area:  6800
NORTH GROUND FLOOR STORE Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   PRINCE STREET,    EAST HOUSTON STREET
Status:   C - JOB IS SIGNED OFF 04/29/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/17/2013 3:13 PM
Application Entered:   05/17/2013 Job Start Date:   05/17/2013
Last Change:   04/29/2014 Job End Date:   06/15/2013
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     04/17/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011398 Licensee Name: JOSEPH FERGUSON
Firm: 003192 Firm Name: AVALON ELECTRIC CORP.
Firm Phone: 718-543-2327  Firm Address: 5760 BROADWAY 2ND FLOOR BRONX NY 10463 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $334.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   ICE CREAM
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: AB BIAGI
Authorized Representative:  ANTONIO BIAGI
Relationship To Owner:   OWNER OF BUSINESS


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  300AMP 3-PH
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3/0 4-WIRE
D. Over 250 MCM  1  350MCM 4WIRE
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  200AMP MLO
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND  STORE  20  30    10  20         
Buildings Total 20  30    10  20              
Total Units : 86 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/17/2013 Notice: 1 - FIRST NOTICE 03/18/2014
Power Issued: 05/17/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ICE CREAM STORE, NEW SERVICE, PANELS AND BRANCH CIRCUITRY.675 SQ.FT.

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: M340562
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/06/2014 03/18/2014 IOS A G (135) (5) Y
INSPECTION COMMENTS: NONE
 
(2) 04/17/2014 04/29/2014 DNM C R E (60) (0) Y
INSPECTION COMMENTS: C

OBJECTION FOR APPLICATION #: M340562
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BSMT: NEUTRAL NOT BONDED IN SERVICE SWITCH
RSLV 03/06/2014 03/06/2014 04/17/2014
 
002 (999) OTHER
NO SUPPLEMENTAL GROUND ROD INSTALLED. 250.53(D)(2)
RSLV 03/06/2014 03/06/2014 04/17/2014
 
003 (999) OTHER
METER NOT JUMPED. 250.52
RSLV 03/06/2014 03/06/2014 04/17/2014
 
004 (999) OTHER
8 AWG CONDUCTORS ARE REIDENTIFIED. 200.6
RSLV 03/06/2014 03/06/2014 04/17/2014
 
005 (999) OTHER
2 WIRES UNDER ONE LUG IN THE TWO DISCONNECTS FOR COMPRESSORS OUTSIDE110.14
RSLV 03/06/2014 03/06/2014 04/17/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.