Electrical Application Details for App #: B378613
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 856 PACIFIC STREET BROOKLYN BIN: 3027662     Block: 1130   Lot: 27
   
Application Completed and Certified

Filed: 856 PACIFIC ST Census Tract:   203 Health Area:  2710
CELLAR Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11238 Community Board:   308
Special Place Name:   ST. JOSEPH'S CHURCH
DOB Cross Street(s):   VANDERBILT AVENUE,    UNDERHILL AVENUE
Status:   C - JOB IS SIGNED OFF 04/27/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/13/2014 1:49 PM
Application Entered:   03/13/2014 Job Start Date:   03/13/2014
Last Change:   04/27/2015 Job End Date:   09/30/2014
Appointment Status:   
Last Inspection By:   JOHN, CHARLES       On     04/23/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011766 Licensee Name: GARY BLANKOPH
Firm: 003683 Firm Name: COGEN ELEC'L SERVICES,INC
Firm Phone: 718-991-6999  Firm Address: 175 CITY ISLAND AVENUE BRONX NY 10464 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $225.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   CHURCH
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: CATHOLIC DIOCESE OF BKLYN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  1 SET OF 4#1'S ELEVATOR
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  400AMP 42 CKT
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    115  10    10  207  48         
Buildings Total 115  10    10  207     48           
Total Units : 390 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/27/2015 Notice: 1 - FIRST NOTICE 03/24/2015
Power Issued: 04/27/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: B378613
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/11/2015 02/17/2015 HRB J (60) (0) Y
INSPECTION COMMENTS: NEED CONTRACTOR TO SHOW ALL WORK
 
(2) 02/27/2015 03/04/2015 PAT J (30) (0) Y
INSPECTION COMMENTS: NEED CONTRACTOR TO SHOW ALL WORK
 
(3) 03/17/2015 03/24/2015 CJE A (65) (7) Y
INSPECTION COMMENTS: N
 
(4) 04/23/2015 04/27/2015 CJH C R E (40) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B378613
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (307) NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT
NO RECEPTACLE OUTSIDE NEAR AC UNITS (ART 210.63)
RSLV 03/17/2015 03/17/2015 04/23/2015
 
002 ( 29) OUTLET BOXES ARE NOT COVERED
BASEMENT MISSING CONDULET CONVER IN BOILER ROOM FOR SMALLER OUTSIDEAC UNIT (ART 314.25)
RSLV 03/17/2015 03/17/2015 04/23/2015
 
003 (999) OTHER
BASEMENT 400 PANEL IN PANTRY MULTI WIRE CIRCUITS MEANS OF DISCONNECTNOT SIMULTANEOUS (ART 210.4)(B)
RSLV 03/17/2015 03/17/2015 04/23/2015
 
004 (999) OTHER
BASE MULTI WIRE CIRCUITS IN PANTRY 400AMP PANEL CIRCUITS NOT GROUPED(ART 210.4)(D)
RSLV 03/17/2015 03/17/2015 04/23/2015
 
005 (999) OTHER
SER ROOM MULTI WIRE CIRCUITS IN B-PP-3 PANEL MEANS OF DISCONNECT NOTSIMULTANEOUS (ART 210.4)(B)
RSLV 03/17/2015 03/17/2015 04/23/2015
 
006 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
BASE NO PANEL DIRECTORY IN PANTRY PANEL & SER ROOM PANELS (ART 408.4)
RSLV 03/17/2015 03/17/2015 04/23/2015
 
007 (151) AIR COND/REFRIG EQUIPMENT NOT PROPERLY MARKED/SIZED/INSTALLED
OUTSIDE AC NOT PROPERLY MARKED OUTSIDE
RSLV 03/17/2015 03/17/2015 04/23/2015