BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A332123
Premises: 32-01 30 AVENUE QUEENS BIN: 4008604     Block: 618   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 3201 30 AV Census Tract:   71 Health Area:  0300
1ST FLOOR KITCHEN Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11102 Community Board:   401
DOB Cross Street(s):    32 STREET,    33 STREET
Status:   C - JOB IS SIGNED OFF 09/09/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/08/2014 12:02 PM
Application Entered:   11/08/2014 Job Start Date:   11/10/2014
Last Change:   09/09/2016 Job End Date:   11/10/2015
Appointment Status:   
Last Inspection By:   DOYLEY, DEXTER       On     08/11/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012172 Licensee Name: GEORGIOS RODAS
Firm: 003883 Firm Name: RODEL ELEC'L CONTR'S, IN
Firm Phone: 718-784-1460  Firm Address: 31-29 VERNON BOULEVARD LONG ISLAND CITY NY 11106 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $41.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: BISCUITERIA
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001      12                 
Buildings Total   12                    
Total Units : 14 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/15/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A332123
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/14/2016 07/15/2016 NRS V (39) (3)
INSPECTION COMMENTS: 2 SWITCH FOR HEAT LAMPS & 10 RECE.S ON EXISTING CIRCUITS. IN KITCHEN.
 
(2) 08/11/2016 08/12/2016 DEX C R (30) (0)
INSPECTION COMMENTS: DISPUTES RESOLVED

OBJECTION FOR APPLICATION #: A332123
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(GROUND FLOOR) COUNTER QUAD ON RIGHT END DOES NOT WORK
RSLV 07/14/2016 07/14/2016 08/11/2016
 
002 ( 19) DEFECTIVE WIRING IS IN USE
(GROUND FLOOR) 2ND FROM RIGHT COUNTER QUAD, LOAD SIDE REVERSE WIRED; UNDER COUNTERQUAD FOR 2 OVEN
RSLV 07/14/2016 07/14/2016 08/11/2016
 
003 (999) OTHER
(GROUND FLOOR) RECE. BOXES SET TOO DEEP 314.20
RSLV 07/14/2016 07/14/2016 08/11/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order