BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z121487
Premises: 110 BENNETT AVENUE MANHATTAN BIN: 1064442     Block: 2180   Lot: 199
  Printable (PDF) version of this Permit  

Filed: 110 BENNETT AV Census Tract:   271 Health Area:  0210
BASEMENT Admin Area:   Z - UPPER MANHATTAN Inspection Area:   A
NEW YORK, NY 10033 Community Board:   112
DOB Cross Street(s):   WEST 186 STREET,    WEST 187 STREET
Status:   P - OBJECTN PENDING AT CONTRACTOR 09/17/2009
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/28/2009 2:41 PM
Application Entered:   04/28/2009 Job Start Date:   05/05/2009
Last Change:   09/17/2009 Job End Date:   07/21/2009
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     09/10/2009      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  

License #: 011701 Licensee Name: ALBERTO SANCHEZ
Firm: 003779 Firm Name: GRX EURO ELECTRIC CORP
Firm Phone: 718-545-0035  Firm Address: 18-02 26TH ROAD ASTORIA NY 11102 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $515.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: NOTHRBROOK PARTNERS
Owner Business Name: NORTHBROOK PARTNETS LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  1  3 SET OF 4. WIRES #500MCM
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  4/2 1/8G-1
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 2 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 04/28/2009 Notice: 1 - FIRST NOTICE 09/17/2009
Power Issued: 04/28/2009 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z121487
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/01/2009 09/04/2009 CLC J (45) (0) Y
INSPECTION COMMENTS: SER TEMP OUT JOB INCOMPLETE
 
(2) 09/10/2009 09/17/2009 DAH A G (30) (3) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z121487
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
BSMT,OPEN SPLICED BOX WITH RISERS
OPEN 09/10/2009 09/10/2009
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
GROUND WIRE NOT PROPERLY INSTALLED AT SVC SW
OPEN 09/10/2009 09/10/2009
 
003 (999) OTHER
JUMPER NOT PROPERLY INSTALLED AT WATER MAIN, NOT A FINAL INSPECTION
OPEN 09/10/2009 09/10/2009



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.